| Technical Specification TE10S |
| Current |
|
|
16A, 25A, 40A and 50A. Under certain conditions e.g. lower ambient temperature these units may be run at slightly
higher currents. Consult your local Eurotherm engineer. |
| Voltage |
|
|
48 to 240 Vac (+10%, -15%) or 96 to 500 Vac (+10%, -15%) |
| Supply frequency |
|
|
47 to 63Hz |
|
| Load |
|
|
|
| Load type |
|
|
Constant resistance or shortwave infrared elements |
| Single phase connection |
|
|
Line-to-line or line-to-neutral |
| Three phase connection |
|
|
Three wire star or delta - two units control two limbs of the load /
Four wire star with neutral or six wire open delta - three units together |
| Firing mode |
|
|
Logic firing (ON/OFF) with zero voltage switching |
|
| Input |
|
|
Polarity insensitive, + and - can be crossed
Command signal indication by green LED |
| Voltage |
|
|
LGC 8 to 32 V dc (ON >8V, OFF <2V)
LAC 32 to 48V ac, (ON >30V, OFF <5V)
HAC 100 to 240Vac, (ON >85V, OFF <10V) |
| Current |
|
|
LGC 9mA dc (Self limiting) (ON>9mA, OFF <0.5mA) |
|
| Option |
|
|
|
| Partial load failure detection |
|
Detects an increase in load impedance due to failure or disconnection of part of the heating load. Discrimination: 1 element in 6 for single phase load |
|
| Installation |
|
|
|
| Dimensions (mm) |
|
|
16A 115H x 35W x 93D (53W with PLF/IPF); 25A 115H x 53W x 93D (70W with PLF/IPF);
40A 115H x 88W x 93D (105W with PLF/IPF); 50A 115H x 105W x 93D (123W with PLF/IPF) |
| Mounting |
|
|
Vertical on DIN rail |
| Inter-unit spacing |
|
|
10mm for full current operation |
| Internal bus bar |
|
|
8mm2 copper bars |
| Power terminals |
|
|
Cable sizes 1.5 to 16mm2. Tightening torque 1.2Nm |
| Control terminals |
|
|
Cable size 0.5 to 1.5mm2. Terminals are removable for easy maintenance |
| Weight |
|
|
16A 320g, 25A 500g, 40A 770g, 50A 880g |
|
| Environment |
|
|
|
| Humidity |
|
|
5 to 95% non condensing |
| Enclosure protection |
|
|
IP20 (IEC 529) |
| Isolation |
|
|
All distances comply with IEC 664
Control signals isolated from power, tested to 3600 Vac. Isolation to earth tested to 2000 Vac |
| Electrical protection |
|
|
RC snubber network
External high speed fuse (to be ordered separately) |
| Leakage current |
|
|
Less than 30 mA |
| Storage temperature |
|
|
-10°C to 70°C |
| Cooling |
|
|
Natural convection |
| Operating temperature |
|
|
0°C to 45°C (up to 60° with derating) |
| Safety standards |
|
|
EN61010, installation category 3 (voltage transients must not exceed 4.0KV) |
| Atmospheres |
|
|
Electrically conductive pollution must be excluded from the cabinet in which this controller is mounted. This product is not
suitable for use above 2000m or in corrosive or explosive atmospheres without further protection. |
|
| European Directives |
|
|
|
| Electromagnetic compatibility |
|
|
| Immunity test standards: |
|
EN61000-4-2, EN 61000-4-4, PrEN 61000-4-3 |
| Emission test standard: |
|
EN 55011, EN50081-2 without external filter (optional parallel filters must be fitted for 2 phase control of 3 phase loads) |
| Safety |
|
|
Complies with the Low Voltage Directive 73/23/EEC dated 19/2/73 amended by Directive 93/68/EEC dated 22/7/93
(product installed and used in compliance with its user manual) |
| CE marking |
|
|
TE10S products carry the CE mark in compliance with the European Low Voltage Directive. A CE declaration of conformity
is available on request. |