Technical Specification TE10S
Current     16A, 25A, 40A and 50A. Under certain conditions e.g. lower ambient temperature these units may be run at slightly higher currents. Consult your local Eurotherm engineer.
Voltage     48 to 240 Vac (+10%, -15%) or 96 to 500 Vac (+10%, -15%)
Supply frequency     47 to 63Hz

Load      
Load type     Constant resistance or shortwave infrared elements
Single phase connection     Line-to-line or line-to-neutral
Three phase connection     Three wire star or delta - two units control two limbs of the load / Four wire star with neutral or six wire open delta - three units together
Firing mode     Logic firing (ON/OFF) with zero voltage switching

Input     Polarity insensitive, + and - can be crossed
Command signal indication by green LED
Voltage     LGC 8 to 32 V dc (ON >8V, OFF <2V)
LAC 32 to 48V ac, (ON >30V, OFF <5V)
HAC 100 to 240Vac, (ON >85V, OFF <10V)
Current     LGC 9mA dc (Self limiting) (ON>9mA, OFF <0.5mA)

Option      
Partial load failure detection   Detects an increase in load impedance due to failure or disconnection of part of the heating load.
Discrimination: 1 element in 6 for single phase load

Installation      
Dimensions (mm)     16A 115H x 35W x 93D (53W with PLF/IPF); 25A 115H x 53W x 93D (70W with PLF/IPF);
40A 115H x 88W x 93D (105W with PLF/IPF); 50A 115H x 105W x 93D (123W with PLF/IPF)
Mounting     Vertical on DIN rail
Inter-unit spacing     10mm for full current operation
Internal bus bar     8mm2 copper bars
Power terminals     Cable sizes 1.5 to 16mm2. Tightening torque 1.2Nm
Control terminals     Cable size 0.5 to 1.5mm2. Terminals are removable for easy maintenance
Weight     16A 320g, 25A 500g, 40A 770g, 50A 880g

Environment      
Humidity     5 to 95% non condensing
Enclosure protection     IP20 (IEC 529)
Isolation     All distances comply with IEC 664
Control signals isolated from power, tested to 3600 Vac. Isolation to earth tested to 2000 Vac
Electrical protection     RC snubber network
External high speed fuse (to be ordered separately)
Leakage current     Less than 30 mA
Storage temperature     -10°C to 70°C
Cooling     Natural convection
Operating temperature     0°C to 45°C (up to 60° with derating)
Safety standards     EN61010, installation category 3 (voltage transients must not exceed 4.0KV)
Atmospheres     Electrically conductive pollution must be excluded from the cabinet in which this controller is mounted. This product is not suitable for use above 2000m or in corrosive or explosive atmospheres without further protection.

European Directives      
Electromagnetic compatibility    
Immunity test standards:   EN61000-4-2, EN 61000-4-4, PrEN 61000-4-3
Emission test standard:   EN 55011, EN50081-2 without external filter (optional parallel filters must be fitted for 2 phase control of 3 phase loads)
Safety     Complies with the Low Voltage Directive 73/23/EEC dated 19/2/73 amended by Directive 93/68/EEC dated 22/7/93 (product installed and used in compliance with its user manual)
CE marking     TE10S products carry the CE mark in compliance with the European Low Voltage Directive. A CE declaration of conformity is available on request.