| TE10P Technical Specification |
| ELECTRICAL |
|
| Nominal current (at 45 Deg. C) |
16A to 400A |
| Nominal voltage |
100V to 500V (+10%, -15%) as product code |
| Supply frequency |
40 to 70 Hz automatic adaptation |
| Electronics supply |
Internal or optionally 115V or 230V external (10VA) |
| Power dissipation |
1.3 watts per amp |
| Fusing |
High speed fuses: External for 16A to 100A (order separately), internal for 125A to 400A |
| Cooling |
Natural cooling up to 100amps Fan cooled from 125 amps upwards (25VA fan) |
| Load |
Any type of single phase load (except capacitive) |
|
|
|
OPERATING |
| Inputs |
0-5V or 0-10V (Input Impedance >100K) |
| |
0-20mA or 4-20mA (input impedance 250 Ohms) |
| Logic: |
5V, 10V or 20mA |
| Digital Comms (optional): |
RS422 or RS485 |
| Firing modes: |
Logic (Onn/Off) |
| |
Burst firing (selectable soft start) |
| |
Advanced Single Cycle |
| |
Phase Angle (selectable ramp) |
| Control mode |
Power - calculated from instantaneous measurements |
| |
RMS voltage |
| |
RMS current |
| |
V2 |
| |
I2 |
| |
Automatic transfer I2 <->P |
| |
Automatic transfer I2 <->V2 |
| |
Open Loop |
| Linearity and stability |
Better than ±1% of full scale |
| Input limit |
Analogue- by potentiometer or by external signal |
| |
Digital- by communications bus (optional) |
| Current or voltage limit |
Either chop-off (with alarm) or revert to phase angle and reduce firing angle |
| Retransmission |
Analogue 0-10V or 4-20mA isolated (accuracy ±1%) |
| |
Digital via comms link |
| Diagnostics |
Diagnostics port available for use with model 260 Diagnostic uni |
|
|
| DIGITAL COMMUNICATIONS |
| Protocol |
PROFIBUS-DP or MODBUS |
|
|
| ALARMS |
| Mains |
Under or over voltage, frequency out of range |
| Load |
Over current or load fault (static or dynamic) |
| Thyristors |
Short circuit or over temperature (fan cooled units) |
|
|
| ENVIRONMENT |
| Temperature |
0 to 45°C operating, -10 to 70°C storage |
| Humidity |
5% to 95% RH Non condensing, non streaming |
| Altitude |
2000 meters maximum |
| Atmosphere |
Non explosive, non conductive and non corrosive |
| Pollution |
Pollution degree 2 admissible, defined by IEC664 |
| Protection (mechanical) |
IP20 on front face according to IEC529 |
| Dimensions |
16 to 100A: 225mm (H) x 116mm (W) x 169mm (D) |
| |
125 to 400A: 470mm (H) x 133mm (W) x 260mm (D) |
| Weight |
16A to 100A: 3.2kg. 125 to 400A: 11.5kg |
| Mounting |
DIN rail mounting up to 100amps |
| |
Bulkhead mounting available for all units |
|
|
| EUROPEAN DIRECTIVES |
| Safety |
The TE10P carries the CE mark to show compliance with the European Low Voltage Directive 73/23/EEC |
| EMC- Immunity |
Conforms to: EN 500082-2, EN 61000-4-2, EN 61000-4-4, ENV 50204, ENV 50140, ENV 50141 |
| EMC- radiated emission |
Conforms to: EN 55011 class A |
| EMC- conducted Emmission |
Conforms to: EN 500081-2 without fiter in Burst Firing modes for resistive loads up to 100amps. An external
filter may be required for other operating conditions |
| |
Conforms to IEC 1800-3 (EN610800-3) without filter |
| |
For use in second (industrial) environment |
| UL approval |
Products ≤100A are UL approved |
|