Ratings: TC1027: 300A, 400A and 500A
120V, 230V, 240V, 400V, 440V,
480V and 500V
TC1028: 300A, 400A, 500A, 750A, 900A,
1200A, and 1650A
100V, 110V, 115V, 120V, 200V, 220V,
230V, 240V, 277V, 380V, 400V, 415V,
440V, 480V, 500V and 690V
Dimensions (mm):   Up to 500A: 570H x 133W x 268D; 10kg
750A: 560H x 373W x 510D
900A/1200A: 560H x 381W x 510D
1650A: 600H x 422W x 302D
Load type:   TC1027: resistive
TC1028: resistive (fixed or variable),
transformer coupled or inductive
Firing mode:   TC1027: fast cycle with supply voltage compensation.
TC1028: fast cycle, single cycle, slow cycle,
fast or slow cycle with soft start, and phase angle (with current limit)
Operating temp:   0°C to 45°C, 5%-95% RH, non-condensing
Mounting:   Panel mounting
Inputs: TC1027: DC Logic-voltage: 10V (>5V ON: <1V
OFF), input impedance 390ž
DC Logic-current: 20mA (>4mA ON:
<0.2mA OFF), input impedance 390ž
AC Logic-voltage: 100V to 264V (>85V
ON: <10V OFF), input impedance 10K
DC Voltage: 0-5V, 1-5V, 0-10V, 2-10V (impedance 68K)
DC Current: 0-20mA, 4-20mA (impedance 250ž)
TC1028: DC Voltage: 0-5V, 1-5V, 0-10V, 2-10V (impedance 50K)
DC Current: 0-20mA, 4-20mA (impedance 250ž)
{short description of image}