Dimensions
inches (mm): |
2.25 (57.1) H x 1.75
(44.5) W x 1.37 (34.8) D when mounted on a vertical panel. |
|
Load type : |
Resistive |
|
SVDADC Input |
|
|
|
DC Logic: 10-25A |
|
ON >4Vdc/5.4mA, 32Vdc/10mA
max. current limited |
|
50-75A |
|
ON >4Vdc/3.5mA, 32Vdc/6.5mA
max. current limited |
|
|
|
OFF <1Vdc |
|
SVAAAC Input |
|
|
|
AC Logic: |
|
ON >100V, 280Vac max. |
|
|
|
OFF <2mA, 10k ohm
impedance |
|
Current ratings: |
|
10A, 25A, 50A and 75A |
|
Voltage
ratings: |
|
3Vxx rating options*; 24V to 330V
max,; 6Vxx rating options*, 24V to 660V max, |
|
Operating
temperature: |
0°C to 40°C (up to 80°C with derating) |
|
Peak blocking
voltage: |
800V, impulse
(300Vac), 1200 (600Vac) |
|
Offstate dVdT: |
300V |
600V |
|
|
10A-750 V/µsec |
50A-500 V/µsec |
|
|
25A-750 V/µsec |
75A-500 V/µsec |
|
|
50A-1000 V/µsec |
|
|
|
75A-1000 V/µsec |
|
|
SOLID STATE RELAY DERATING CURVES |
|
Graphs are Watts
of heat generated (Y) vs. RMS on-state current in amps (X) |
|
|
|
 |
|
10 Amp Relay
Recommended heatsink: S505-heatsk-2.1 or S505-heatsk-din (DIN rail
mounted) |
|
25 Amp
Relay Recommended heatsink: S505-heatsk-1.5 or S505-heatsk-din (DIN
rail mounted) |
|
 |
|
 |
|
50 Amp Relay
Recommended heatsink: S505-heatsk-1.0 |
|
75 Amp