- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  

RVD3/RVA3 DIN Rail Mounted
Three Phase Solid State Contactor



SPECIFICATIONS

INPUT
DC Input (L) ON >=4Vdc/10mA, 32Vdc/15mA max, current limited
OFF <=1Vdc
DC Input (H) ON >=10Vdc/3.5mA, 60Vdc/6mA max, current limited
OFF <=1Vdc
AC Input (H) ON >=100V/9mA, 280Vac/30mA max
OFF <- 2mA, 10k ohm impedance

OUTPUT
Current Ratings 25 amps (3 pole), 35 amps (2 pole)
Voltage Rating 5V option: 24V to 575Vac max. (internal MOV)
6V option: 24V to 660Vac max.
Frequency 47-63 Hz
Voltage Drop 3.0 Vac
I2T Fusing (8.3 msec) 1350 A2sec
Leakage @ VOUT (max.) 10 mA max.
Holding Current 100 mA
Peak Blocking Voltage 1400 Vac
Offstate dVdt 1000 V/µsec
Dielectric Strength 4000 Vrms

OPERATING TEMPERATURE
Ambient Temperature Range (Operating) 0°C to 40°C (up to 80°C with derating)

{short description of image}
Last Updated Friday, July 29, 2005