TECHNICAL SPECIFICATIONS

POWER  
Current 16, 25, 40, 63, 80, 100, 125, 160, 200, 250amps single phase at 45 Deg. C
Voltage 100Vac to 500VAC (+10%, -15%)
Frequency 47 to 63 Hz
   
AUXILIARY SUPPLY No Auxiliary supply is required as the 7100S derives its own internal, synchronized supply
   
FAN SUPPLY None required up to 200 amps (natural convection). For 250 amp units; 115V or 230V (10VA)
   
LOAD Single Phase industrial load:
Use category AC-51 Resistive load with low temperature coefficient
  AC-55b Short wave infrared elements up to 100 amps. The load can be switched line to neutral or line to line - select appropriate volt
   
FUSES High speed fuses are external for thyristor ratings up to and including 100 amps, internal above 100amps
  The fuses can be called up as part of the ordering code (High speed fuses not recommended for SWIR loads)
 
INPUT DC Logic (LDC) 4.5 to 32 VDC (ON > 4.5V, OFF < 2V) or (ON > 9mA, OFF < 0.5mA) 32VDC maximum.
  AC Logic (HAC) 100 to 230VAC (ON > 85VAC, OFF < 10VAC) 253VAC maximum. Impedance 7KΩ at 50 Hz
  DC analogue (ATP) 4-20mA (10VDC max.)
   
FIRING MODE For Logic inputs the firing is ON/OFF with zero voltage switching. Intelligent half cycle firing available if input is from a Eurotherm REMIO interface unit.
  For analogue 4-20mA input the firing mode is Fast Cycle firing. The cycle time at 50% demand is 0.6 seconds (0.3 seconds ON and 0.3 seconds OFF). Output linearity better than + or - 2%. Open loop control (no supply voltage compensation)
   
INDICATION Green LED for supply ‘ON’. Green LED for Heat ‘ON’. Plus a range of diagnostic indicators
   
ALARMS (OPTION)  
Serious alarms (GRF) Unit over temperature thyristor short circuit, load open circuit signaled by set LED and relay contact
Diagnostic alarms (DLF)  
  Partial load failure signaled by DLF LED and relay contact. The DLF option includes serious alarm monitoring (GRF)
  Sensitivity: Detects the failure of at least one heating element for up to six LTCL or four SWIR identical elements connected in parallel
   
ENVIRONMENT  
Temperature Operating: 0 to 45 Deg. C. (2,000 metres maximum altitude). Storage: -10 to 70 Deg. C
Humidity 5 to 95% Non condensing, non streaming
Pollution Pollution degree 2
Enclosure protection. IP20 without additional protection
Cooling Natural convection up to 200 amps, fan cooled for 250amps
Heat dissipation 1.3W per amp (≤2W if internal fuse)
Over-voltage Installation category II
   
DIGITAL COMMUNICATION
  Optional Modbus communication running at 9600 or 19200 baud, allows the units to be controlled and monitored by a supervisory system
   
INSTALLATION  
Mounting. Rating from 16 to 63A: Two symmetric DIN rail EN50022 or bulkhead mounting (4 x M4 screws)
  Rating from 80 to 100A: Bulkhead mounting (4 x M4 screws)
  Rating from 125 to 200A: Bulkhead mounting (4 x M6 screw
  Allow a minimum of 10mm between units. Units must be mounted with fins running vertically
Max. cable size. 16 and 25 amp: 6mm2. 40 and 63 amp: 16mm2. 80 and 100 amp: 35mm2. 125 to 200 amp: 120mm2
   
PRODUCT STANDARD The 7100S products comply with the terms of product standard EN 60947-4-3. Contactors and motor-starters - AC semiconductor controllers and contactors for non-motor loads.
   
CE LABELING 7100S units installed and used according to user instructions and comply with the requirements of the European Low Voltage Directive 73/23EEC (93/68 EEC) and product standards. This enables the installation in which the products are used to be declared compliant with the EMC directive, as regards the 7100S units.
   
WARRANTY 2 years
   
Rating (A) H(mm) W(mm) D(mm) Max. Weight Kg
Basic Options Basic Options Options
16 164 35 52.5 110 135 0.56
25 164 35 52.5 110 165 0.7
40 164 52.5 52.5 140 165 0.9
63 164 70 70 160 185 1.45
80-100 226 96 96 164 189 1.85
125-200 424 144 144 285 285 5.6
250 424 144 144 285 285 6.0
{short description of image}