- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  

TECHNICAL SPECIFICATIONS

POWER  
Current 16, 25, 40, 63, 80 and 100 amps single phase at 45 degrees C.
Voltage 230V (48-253V), 500V (96-550V)
Frequency 47 to 63 Hz
   
LOAD  
Load type Constant resistance single phase load, switched Line to Neutral or Line to Line.- Select appropriate voltage
   
FUSE An external fuse is necessary in order to protect the solid state contactor (see the Ordering code)
   
INPUT  
DC Logic (LDC). 5 to 32 VDC (ON > 5V, OFF < 2V) or (ON > 9mA, OFF < 0.5mA).
AC Logic (HAC) 100 to 230VAC (ON > 85VAC, OFF < 10VAC) 253VAC maximum. Impedance 7K at 50 Hz.
   
FIRING MODE Logic firing (ON/OFF) with zero voltage switching.
   
INDICATION Green 'HEAT' LED on front face indicates the presence of the input signal.
   
ENVIRONMENT  
Temperature Operating: 0 to 45 Deg. C. (2,000 meters maximum altitude).
  Storage: -10 to 70 Deg. C.
Pollution Pollution degree 2
Humidity 5 to 95% Non condensing, non streaming.
Enclosure protection. IP20 without additional protection.
Cooling Natural convection.
Heat dissipation 1.3 watts per amp. Allow 2 watts per amp to include heat dissipation from fuse (if used).
Safety standards Installation category II
   
INSTALLATION  
Mounting. Allow a minimum of 10mm between units. Unit must be mounted with fins running vertically.
  Rating from 16 to 63A: one symmetric DIN rail EN50022 or panel mounting (2 x M4 screws).
  Rating from 80 to 100A: two symmetric DIN rail EN50022 (125mm between centers) or panel mounting (4 x M4 screws)
Max. cable size. 16 and 25 amp: 6mm2. 40 and 63 amp: 16mm2. 80 and 100 amp: 35mm2
   
PRODUCT STANDARD The 7100L products comply with the terms of product standard EN 60947-4-3. Contactors and motor-starters - AC semiconductor controllers and contactors for non-motor loads.
   
CE LABELING 7100L units installed and used according to User Instructions document HA176385FED comply with the requirements of the European Low Voltage Directive73/23EEC (93/68 EEC) and product standard EN60947-3. This enables the installation in which the products are used to be declared compliant with the EMC directive, as regards the 7100L units.
   
WARRANTY 2 years
   
  H(mm) W(mm) D(mm) Weight Kg
16A 164 35 110 0.3
25A 164 35 140 0.45
40A 164 52.5 140 0.68
63A 164 70 160 0.9
80A - 100A 226 96 164 1.56