| POWER |
|
| Current |
16, 25, 40, 63, 80 and 100 amps single phase at 45 degrees C. |
| Voltage |
230V (48-253V), 500V (96-550V) |
| Frequency |
47 to 63 Hz |
| |
|
| LOAD |
|
| Load type |
Constant resistance single phase load, switched Line to Neutral or Line to Line.- Select appropriate voltage |
| |
|
| FUSE |
An external fuse is necessary in order to protect the solid state contactor (see the Ordering code) |
| |
|
| INPUT |
|
| DC Logic (LDC). |
5 to 32 VDC (ON > 5V, OFF < 2V) or (ON > 9mA, OFF < 0.5mA). |
| AC Logic (HAC) |
100 to 230VAC (ON > 85VAC, OFF < 10VAC) 253VAC maximum. Impedance 7K at 50 Hz. |
| |
|
| FIRING MODE |
Logic firing (ON/OFF) with zero voltage switching. |
| |
|
| INDICATION |
Green 'HEAT' LED on front face indicates the presence of the input signal. |
| |
|
| ENVIRONMENT |
|
| Temperature |
Operating: 0 to 45 Deg. C. (2,000 meters maximum altitude). |
| |
Storage: -10 to 70 Deg. C. |
| Pollution |
Pollution degree 2 |
| Humidity |
5 to 95% Non condensing, non streaming. |
| Enclosure protection. |
IP20 without additional protection. |
| Cooling |
Natural convection. |
| Heat dissipation |
1.3 watts per amp. Allow 2 watts per amp to include heat dissipation from fuse (if used). |
| Safety standards |
Installation category II |
| |
|
| INSTALLATION |
|
| Mounting. |
Allow a minimum of 10mm between units. Unit must be mounted with fins running vertically. |
| |
Rating from 16 to 63A: one symmetric DIN rail EN50022 or panel mounting (2 x M4 screws). |
| |
Rating from 80 to 100A: two symmetric DIN rail EN50022 (125mm between
centers) or panel mounting (4 x M4 screws) |
| Max. cable size. |
16 and 25 amp: 6mm2. 40 and 63 amp: 16mm2. 80 and 100 amp: 35mm2 |
| |
|
| PRODUCT STANDARD |
The 7100L products comply with the terms of product standard EN 60947-4-3. Contactors and motor-starters - AC semiconductor
controllers and contactors for non-motor loads. |
| |
|
| CE LABELING |
7100L units installed and used according to User Instructions document HA176385FED comply with the requirements of the
European Low Voltage Directive73/23EEC (93/68 EEC) and product standard EN60947-3. This enables the installation in which the
products are used to be declared compliant with the EMC directive, as regards the 7100L units. |
| |
|
| WARRANTY |
2 years |
| |
|
| |
H(mm) |
W(mm) |
D(mm) |
Weight Kg |
| 16A |
164 |
35 |
110 |
0.3 |
| 25A |
164 |
35 |
140 |
0.45 |
| 40A |
164 |
52.5 |
140 |
0.68 |
| 63A |
164 |
70 |
160 |
0.9 |
| 80A - 100A |
226 |
96 |
164 |
1.56 |
|