Ratings: |
Current: |
15A, 25A, 40A, 63A, 75A, 100A and 125A |
|
Voltage: |
120V, 240V, 415V, 440V, 480V and 500V |
| Dimensions (mm): |
|
15A: 134H x 98W x 94D, t 0.6kg |
|
|
25A: 134H x 98W x 130D, 0.8kg |
|
|
40A/63A: 134H x 116W x 155D, 1.2kg |
|
|
75A/100A/125A: 190H x 117W x 190D, 2.0kg |
| Load type: |
425S: |
resistive, short wave infrared (req. REMIO) |
|
425A: |
resistive (fixed or variable), short wave
infrared or inductive |
| Inputs: |
425S: |
DC Logic-voltage: 10V (>8V ON: <2V |
|
|
OFF) 320 or 24V (>16V ON : <2V |
|
|
OFF), input impedance 1.6K |
|
|
DC Logic-current : 20mA (>5mA ON: |
|
|
<0.5mA OFF), input impedance 10 |
|
|
AC Logic-voltage: 24V (>20V ON: <6V |
|
|
OFF) 2K or 48V (>30V ON: <10V OFF),
|
|
|
input impedance 3K 240V (>90V ON: |
|
|
<35V OFF), input impedance 9.3K |
|
425A: |
DC voltage: 0-5V (70K), 1-5V (75K), 0- |
|
|
10V (85K) use 0-5V for manual control |
|
|
DC current: 0-5mA (impedance 1K), 0- |
|
|
10mA (imp. 470), 0-20mA (imp.
270), |
|
|
4-20mA (imp. 270) |
| Firing mode: |
425S: |
zero voltage switching |
|
|
(synchronized to line) |
|
425A: |
fast cycle, single cycle, slow cycle and |
|
|
phase angle (with optional current limit) |
| Operating temp: |
|
0°C to 45°C |
| Mounting: |
|
Panel, symmetrical or asymmetrical DIN rail |