Factory Mutual (FM) Approved High Limit Alarm Units
Models 2216e, 2208e and 2204e

TECHNICAL SPECIFICATION
Supply voltage: 100 to 240Vac -15%, +10%
Supply frequency: 48 to 62Hz
Power consumption: 10Watts maximum
Relay ratings: Min: 100mA at 12Vdc. Max: 2A resistive at 264Vac
Leakage current: The leakage current through the external snubber supplied to suppress voltage spikes on relay contact outputs is less than 2mA at 264Vac, 50Hz
Over current protection: External over current protection devices are required that match the wiring of the installation
Wire size A minimum of 0.5mm2 or 16awg wire is recommended
Fusing Use independent fuses for the instrument supply and each relay output. Suitable fuses are T type, (IEC 127 time-lag type) as follows;
Instrument supply: 85 to 264Vac, 2A, (T)
Relay outputs: 2A (T).
Low level I/O: All other input and output connections are intended for low level signals at less than 42V
ENVIRONMENTAL RATINGS
Panel sealing: The alarm unit is intended to be panel mounted. The rating of panel sealing is defined by EN 60529: IP 65
Operating temperature: 0 to 55 degrees C. Ensure the enclosure provides adequate ventilation
Relative humidity: 5 to 90%, non condensing
Atmosphere: The instrument is not suitable for use above 2000m or in explosive or corrosive atmospheres
ELECTRICAL SAFETY
Safety Standard: Meets EN 61010, Installation category II, pollution degree 2 Voltage transients on any mains power connected to the instrument must not exceed 2.5kV
Electrically conductive pollution must be excluded from the cabinet in which the instrument is mounted
Isolation: All isolated inputs and outputs, have a reinforced isolation which provides protection against electric shock.
Non-isolated logic connections are electrically connected to the main process variable input, (e.g. the thermocouple)