TECHNICAL
SPECIFICATION (2408i) |
| Main process value input and second
DC input |
| Low level range |
|
|
-100 to +100mV |
| High level
range |
|
0-20mA or
0-10Vdc |
| Sample rate |
|
|
9Hz |
| Resolution |
|
<2µV for low level
inputs |
|
|
<0.2mV
for high level inputs |
| Linearity |
|
|
Better than 0.2°C |
| Calibration accuracy |
|
|
±0.2%
of reading, or ±1°C or ±1LSD, whichever is the greater |
| User
calibration |
|
|
Low and high offsets can be
applied |
| Input filtering |
|
|
OFF to 999.9
seconds |
| Cold
Junction compensation |
|
In automatic mode, >30 to 1
rejection of ambient temperature change OR external 0°C, 45°C, 50°C
external references |
| 3-wire Pt100 input |
|
|
Bulb
current: 0.3mA. Up to 22ohm in each lead without error |
| 2nd
analogue input functions |
|
2nd process value, remote
setpoint, select min, select max, derived value |
| Custom curve |
|
|
15 point,
user selectable |
Digital inputs |
| Contact closure or open collector inputs |
| Note: these are
powered by the controller |
| Digital inputs 1 & 2 |
Switching voltage/current: |
|
24Vdc/20mA
nominal |
| (Non
isolated from PV) |
|
Off state resistance
<100ohms |
|
|
|
On state
resistance >28Kohm |
| Triple contact closure inputs (isolated) |
|
Specification is as per
digital inputs 1 & 2 |
| Externally powered inputs |
| Triple logic
inputs |
Off state: |
|
<5Vdc |
|
On state: |
|
10.8 to
30Vdc @ 2.5mA |
| Digital
input functions |
|
|
| Power consumption 15W max. As per digital inputs 1 & 2 in
the ordering code |
Digital
outputs |
| Relay rating |
|
|
2A, 264Vac
resistive |
| Triple logic
output |
|
|
8mA, 12Vdc per channel |
| Digital output functions |
|
As per the
ordering code |
| DC retransmission |
|
|
| Range |
|
|
Scaleable
between 0-20mA and 0-10Vdc |
| Resolution |
|
|
1 part in 10,000 |
| Retransmission values |
|
Process
value, setpoint or error from setpoint |
Transmitter
supply |
| Rating |
|
|
20mA,
24Vdc |
Strain gauge
bridge supply |
| Bridge voltage |
|
|
Software
selectable, 5 or 10Vdc |
| Bridge
resistance |
|
|
300W to 10KW |
Alarms |
| Number of
alarms |
|
|
Four |
| Alarm types |
|
|
High, low,
deviation high, deviation low, deviation band, rate of change in units/sec,
rate of change in units/min. New alarm status. Sensor break alarm. |
| Selecatble |
|
|
On input 1, input 2 and main
PV. |
| Alarm modes |
|
|
Latching or
non-latching. Blocking. |
|
|
|
Energised or de-energised in
alarm |
| Alarm delay |
|
|
OFF to 999.9
secs |
Communications |
| Module types |
|
|
RS232,
2-wire RS485 and 4-wire RS485 |
| Protocols |
|
|
Modbus®, EI-Bisynch
(ASCII) or Profibus-DP |
PDSIO |
| Functions |
|
|
Remote setpoint input from
master controller |
General |
| Display
colour |
|
|
Red or green |
| Number of digits |
|
|
Five with up
to three decimal places |
| Supply |
|
|
100 to 240Vac -15%, +10% OR
24Vdc or ac -15%, +20%. |
| Power consumption |
|
|
15W
max. |
| Operating
ambient |
|
|
0 to 55°C and 5 to 95% RH
non-condensing |
| Storage temperature |
|
|
-10 to
+70°C |
| Panel
sealing |
|
|
IP65 |
| Dimensions (mm) |
|
|
96W x 48H x
150D |
| Weight |
|
|
400g max |
| EMC standards |
|
|
EN50081-2
& EN50082-2 generic standards for industrial environments |
| Safety
standards |
|
|
Meets EN61010, installation
category II, pollution degree 2 |
| Atmospheres |
|
|
Not suitable
for use above 2000m or in explosive or corrosive atmospheres. |