2408i Universal Process Indicator and Alarm Unit


TECHNICAL SPECIFICATION (2408i)
Main process value input and second DC input
Low level range -100 to +100mV
High level range 0-20mA or 0-10Vdc
Sample rate 9Hz
Resolution <2µV for low level inputs
<0.2mV for high level inputs
Linearity Better than 0.2°C
Calibration accuracy ±0.2% of reading, or ±1°C or ±1LSD, whichever is the greater
User calibration Low and high offsets can be applied
Input filtering OFF to 999.9 seconds
Cold Junction compensation In automatic mode, >30 to 1 rejection of ambient temperature change OR external 0°C, 45°C, 50°C external references
3-wire Pt100 input Bulb current: 0.3mA. Up to 22ohm in each lead without error
2nd analogue input functions 2nd process value, remote setpoint, select min, select max, derived value
Custom curve 15 point, user selectable

Digital inputs
  Contact closure or open collector inputs
Note: these are powered by the controller
Digital inputs 1 & 2 Switching voltage/current: 24Vdc/20mA nominal
(Non isolated from PV) Off state resistance <100ohms
On state resistance >28Kohm
Triple contact closure inputs (isolated) Specification is as per digital inputs 1 & 2
Externally powered inputs
Triple logic inputs Off state: <5Vdc
On state: 10.8 to 30Vdc @ 2.5mA
Digital input functions
Power consumption 15W max. As per digital inputs 1 & 2 in the ordering code

Digital outputs
Relay rating 2A, 264Vac resistive
Triple logic output 8mA, 12Vdc per channel
Digital output functions As per the ordering code
DC retransmission
Range Scaleable between 0-20mA and 0-10Vdc
Resolution 1 part in 10,000
Retransmission values Process value, setpoint or error from setpoint

Transmitter supply
Rating 20mA, 24Vdc

Strain gauge bridge supply
Bridge voltage Software selectable, 5 or 10Vdc
Bridge resistance 300W to 10KW

Alarms
Number of alarms Four
Alarm types High, low, deviation high, deviation low, deviation band, rate of change in units/sec, rate of change in units/min. New alarm status. Sensor break alarm.
Selecatble On input 1, input 2 and main PV.
Alarm modes Latching or non-latching. Blocking.
Energised or de-energised in alarm
Alarm delay OFF to 999.9 secs

Communications
Module types RS232, 2-wire RS485 and 4-wire RS485
Protocols Modbus®, EI-Bisynch (ASCII) or Profibus-DP

PDSIO
Functions Remote setpoint input from master controller

General
Display colour Red or green
Number of digits Five with up to three decimal places
Supply 100 to 240Vac -15%, +10% OR 24Vdc or ac -15%, +20%.
Power consumption 15W max.
Operating ambient 0 to 55°C and 5 to 95% RH non-condensing
Storage temperature -10 to +70°C
Panel sealing IP65
Dimensions (mm) 96W x 48H x 150D
Weight 400g max
EMC standards EN50081-2 & EN50082-2 generic standards for industrial environments
Safety standards Meets EN61010, installation category II, pollution degree 2
Atmospheres Not suitable for use above 2000m or in explosive or corrosive atmospheres.