TECHNICAL SPECIFICATION |
| Display: |
|
4 digit, green, 10mm high characters |
| Supply voltage: |
|
|
85-264Vac, 48-62Hz, or 20-29Vac/dc, 5watts max |
| Operating ambients: |
|
0-55°C, 5-95%RH non-condensing |
| Output ratings: |
Logic: |
|
9Vdc, 12mA (non-isolated) (Can be used as alarm output or alarm acknowledge input) |
|
Relay: |
|
2A, 264V ac resistive |
| Calibration accuracy: |
|
± 1°C or ± 0.25% of reading whichever is greater |
| Cold junction compensation: |
|
>30 to 1 rejection of ambient temperature change |
| Input filtering: |
|
|
Off-999.9 seconds |
| EMC standards: |
|
|
Meets generic emissions standard EN50091-2 and immunity standard EN50082-2 for industrial environments |
| Safety standard: |
|
|
Meets EN61010, installation category II Pollution degree 2 |
| Atmospheres: |
|
|
Not suitable for use above 2000m or in explosive or corrosive atmospheres |