7SL 1/16 DIN Limitrol FM Approved Safety Limit


Supply Voltage: 100-240 Vac (+10%, -15%), 50/60 Hz
or 24 Vac/Vdc (±10%)
Operating Ambient: 0-50°C, 20-85% RH non-condensing
Inputs: T/C Types J, K, T, E, N, S, R, B, L, U, G, D, C
& Platinel II (°C, °F); Pt 100 3W RTD (°C, °F)
Ranges: See Table B, page 2-10; mAdc, mVdc, Vdc
Logic Input: requires contact rated at 0.5 mA, 5 Vdc minimum
Output Ratings:
Output 1: Relay, Form C, 3A/250V, Resistive
High Limit, Low Limit, High/Low Limit
Alarm 1, Failsafe, FM Approved
Output 2: Optional Relay, Form A, 2A/250V, Resistive
Process, Band, Deviation Alarm
Alarm 2, Direct or Reverse Acting
Serial Comms: EIA RS-485 Modbus®, JBUS
Mounting: Panel Mount or optional DIN Rail/Wall Mount

Thermocouple and RTD Input Range Table
Input Type °C Range °F Range
TC J -100 to 1000 -150 to 1830
TC K -100 to 1370 -150 to 2500
TC T -200 to 400 -330 to 750
TC E -100 to 800 -150 to 1470
TC N -100 to 1400 -150 to 2550
TC S -50 to 1760 -60 to 3200
TC R -50 to 1760 -60 to 3200
TC B 0 to 1820 32 to 3300
TC L -200 to 900 -330 to 1650
TC U -100 to 600 -150 to 1110
TC G 0 to 2300 0 to 4170
TC D 0 to 2300 0 to 4170
TC C 0 to 2300 0 to 4170
TC Platinel II -100 to 1400 -150 to 2550
RTD Pt100 -200 to 850 -330 to 1560

Failsafe Mode
The FM approved Form C relay operates in a failsafe mode. During powerup, the relay is off and can be selected to restart either manually or automatically. In normal operation when an alarm occurs and the relay resets, the process can be restarted by

operator actions as prescribed by process and configuration conditions. In order to restart, the process must return within setpoint AND the operator must acknowledge the process either by the front panel, digital input or serial link.

 