7HL 1/8 DIN High Performance Digital Indicator |
|
Supply Voltage: |
100-240 Vac (+10%, -15%), 50/60
Hz |
|
Operating Ambient: |
0-50°C, 20-85% RH non-condensing |
|
Inputs: |
T/C Types B, E, J, Fe-CuNi, K,
R, S, T, Cu-CuNi, N, W, W3, W5,Ni/Ni-Mo and |
|
|
Platinel II (°C, °F); Pt 100 3W RTD
(°C, °F) |
|
|
Ranges: mAdc, mVdc, Vdc |
|
Logic Input: |
(Open=Local Front Panel; Closed=Remote |
|
|
Serial Link) requires contact
rated at 0.5 mA, 5 Vdc minimum |
|
Serial Communications: |
EIA RS-485 Modbus®, JBUS |
|
Aux. Power Supply: |
Isolated 5, 10, 12 or 24 Vdc
(Jumper Selectable), |
|
|
25 mAdc max. current, Accuracy ±5% of
nominal |
|
Output Ratings: |
|
|
Output 1: |
|
Relay, 2A/30 Vdc; 0.6A/110 Vdc; 0.5A/250 Vac |
|
|
SPST, NO or NC Jumper
Selectable, Resistive |
|
|
Relay, 0.3A/110 Vdc, SPST, NO or NC Jumper |
|
|
Selectable, Inductive |
|
|
Alarm 1, Direct or Reverse |
|
Output 1: |
|
Relay, 2A/30 Vdc; 0.6A/110 Vdc;
0.5A/250 Vac |
|
|
SPST, NO or NC Jumper Selectable, Resistive |
|
|
Relay, 0.3A/110 Vdc, SPST, NO
or NC Jumper Selectable, Inductive |
|
|
Alarm 2, Direct or Reverse |
|
Retranmission |
|
|
|
Output: |
|
0 to 20 mA or 4 to 20 mA, Isolated (500W
max.) |
|
|
0 to 10 Vdc, Isolated (5kW min.) |
|
|
Retransmission of PV |
|
Mounting: |
Panel Mount |
| Thermocouple and RTD Input Range Table |
| Input Type |
°C Range |
°F Range |
| TC B |
0 to 1820 |
32 to 3300 |
| TC E |
-199.9 to
800.0 |
-328 to
1470 |
| TC J |
-199.9 to 999.9 |
-328 to 1860 |
| TC Fe-CuNi |
-199.9 to
900.0 |
-328 to
1650 |
| TC K |
-199.9 to 1370 |
-328 to 2500 |
| TC R |
-50 to 1760 |
-58 to 3200 |
| TC S |
-50 to 1760 |
-58 to 3200 |
| TC T |
-199.9 to
400.0 |
-328 to 750 |
| TC Cu-CuNi |
-199.9 to 6.00.0 |
-328 to 1110 |
| TC N |
0 to 1300 |
32 to 2370 |
| TC W |
0 to 2310 |
32 to 4190 |
| TC W3 |
0 to 2310 |
32 to 4190 |
| TC W5 |
0 to 2310 |
32 to 4190 |
| TC NiNi-Mo |
0 to 1200 |
32 to 2192 |
| TC Platinel II |
0 to 1400 |
14 to 2550 |
| RTD Pt100 |
-199.9 to
850.0 |
-328 to
1560 |
| RTD Pt100 |
-60.0 to 350.0 |
-76 to 660 |
|
| |
|
|
Optional Features In addition
to its standard features, the 7HL has 3 important optional features:
- Digital communications featuring an opto-isolated EIA
RS-485 communications port with Modbus® or JBUS protocol (this option is
not available with the retransmission output). A closed logic input enables
remote operation from the serial link; an open logic input enables local
operation from the front panel.
|
- An auxiliary power supply for powering external
transducers. Jumper selected isolated outputs at 5, 10, 12 or 24 Vdc (25 mA
max.) are available.
- A linear analog retransmission output of the process
variable is available as an isolated, 0 to 20 mA, 4 to 20 mA or 0 to 10 Vdc
signal. This output is programmable and can have a digital filter applied to
the retransmission.
|
|