GENERAL TECHNICAL SPECIFICATION (K1E)
Dimensions: 100 x 150 mm, depth 88 mm.
Control modes: On/Off, PID, PID + SMART
Weight: 130 g max.
Supply: 85 V to 265 V AC 50/60 Hz 6V A (max)
Isolation: 2300 V RMS according to EN 61010-1.
Sample/Display update: 500 ms.
Accuracy: + 0,3% f.s.v. + 1 digit @ 25 °C ambient and nominal power supply.
Operating temperature range: from 0 to 50 °C.
Storage temperature range: from -20 to +85 °C
Operating humidity range: from 20 % to 85% RH, non condensing.
Control output type: time proportioning.
Output cycle time: from 1 to 200 s.
Input types: L, J, K, N, T, R, S thermocouples; PT100 3-wire RTD