- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  

X26 Environmental Chamber Controller


TECHNICAL SPECIFICATION (X26)
Temperature inputs (Wet and Dry bulbs):
Input types: J,K,T,L,N thermocouples. 3-wire, Pt100
Accuracy: + 0.1%
Sample rate: 9Hz
Cold Junction Compression: >30 to 1 rejection of ambient temp. change
3-wire Pt. 100 inputBulb current: 0.3mA. Up to 22ohm in each lead without error
Humidity probe input:
Probe trans supply: 24Vdc, 20mA max
Input signal range: 0-1Vdc or 0-10Vdc (equivalent to 0-100%Rh)
Accuracy: +0.1%
Run, hold and reset digital inputs:
Open circuit voltage: 4Vdc nominal
Closed circuit current: 0.8mA nominal
Heating, cooling, humidifying and dehumidifying outputs:
Relay rating: 2A, 264Vac resistive
Logic output: 8Vdc, 12mA
Triac outputs: 1A, 264Vac max
DC outputs: 0-20mA or 0-10Vdc
Temperature and humidity retransmission outputs:
Range: 0-20mA or 0-10VDC (isolated)
Resolution: 12 bits
Control Functions:
Control mode: PID
Tuning: Automatic one-shot tuning
Auto manual control: Bumpless transfer between auto and manual
Alarms:
Number of alarms: One high temperature alarm
Setpoint programming
Number of programs: 50
Number of setpoints: 500
Event outputs: 2
Program holdbacks: high and low holdback settable per segment
Communications:
Modbus: RS232, RS422 or RS485 (2 or 4-wire)
General:
Display range: Five digits with one decimal place
Supply: 100 to 240Vac - 15%. + 10%
Operating ambient: 0 to 55oC and 5 to 95% RH non-condensing
Storage temperature: -10 to + 70oC
Panel sealing: IP65
Dimensions(mm) : 96W x 96H x 150D
EMC standards: Meets generic emissions standards
EN500081-2 and immunity standard
En50082-2 for industrial environments
Safety standards: Meets En61010, installation category II, pollution degree 2
Last updated January 7, 2004