General SPECIFICATION Mini8 |
| Control features |
|
4, 8 or 16 Loops with AutoTune, Dual Channel OP with various cooling
modes, PID, OnOff, Auto/Man, Feedforward, 3 PID sets,
Remote SP, Forced manual, Sensor break OP, SP ramp, OP rate limit,
Heater failure detection |
| Communications |
|
Network: Modbus RTU (EIA485),
Ethernet (modbus TCP), Profibus DP,
DeviceNet, CANopen
Config: Modbus RTU (EIA232), can be used as second network port |
| Standard IO |
|
2 off 24Vdc Logic inputs with 42Vac/dc system isolation, 2 off 1Amp
Change over relays (42Vac/dc max) |
| TC4/TC8 Module |
|
4/8 Channels, Range: –70mV to 70mV, Accuracy ±1OC ±0.1% of
reading, T/C types: C, J, K, L, R, B, N, T, S, LINEAR, Custom, CJC >30:1,
42Vac/dc Channel isolation, Input impedance >100M |
| RT4 Module |
|
2, 3, or 4 wire input, PT100 RTD or linear |
| DO8 Module |
|
8 Channels, Supply: 15vdc-30Vdc, On/Off, Time Proportioning,
Common 42Vac/dc system isolation |
| DI8 Module |
|
8 Channel logic input with 42Vac/dc system isolation |
| CT3 Module |
|
3 Channels,
Current Input Range 0-50mA rms, Accuracy:
±2% of span, No isolation, Overload current: 300mA,
1 CT3 per Mini8 |
| RL8 Module |
|
8 Channel Form A relay (NO) max 2A @ 264Vac |
| AO4/AO8 Module |
|
4 or 8 Channels, Range 0-20mA, 360R load, 42Vac/dc channel isolation |
| SP Programmer |
|
8 Programmers, 16 Segments and 8 Events each, External Run,
Hold, Reset, Skip Segment, Advance segment |
| Maths & Logic |
|
24 x 2 Input Maths, 24 x 2 Input Logic, 4 x 8 Input logic, 4 x 8 input
multiplexor, 32 User Values, 4 x 8 Multiple Input |
| Recipes |
|
8 Recipes, 24 tags in each |
| Timer Functions |
|
8 Timers, 2 Counters, 2 totalizers, Non-volatile real time clock |
| Power Supply (2500P Recommended) |
|
17.8Vdc-28.8Vdc, Power consumption 15W max, 10W typical |
| Approvals |
|