General SPECIFICATION Mini8
Control features 4, 8 or 16 Loops with AutoTune, Dual Channel OP with various cooling modes, PID, OnOff, Auto/Man, Feedforward, 3 PID sets, Remote SP, Forced manual, Sensor break OP, SP ramp, OP rate limit, Heater failure detection
Communications Network: Modbus RTU (EIA485), Ethernet (modbus TCP), Profibus DP, DeviceNet, CANopen Config: Modbus RTU (EIA232), can be used as second network port
Standard IO 2 off 24Vdc Logic inputs with 42Vac/dc system isolation, 2 off 1Amp Change over relays (42Vac/dc max)
TC4/TC8 Module 4/8 Channels, Range: –70mV to 70mV, Accuracy ±1OC ±0.1% of reading, T/C types: C, J, K, L, R, B, N, T, S, LINEAR, Custom, CJC >30:1, 42Vac/dc Channel isolation, Input impedance >100M
RT4 Module   2, 3, or 4 wire input, PT100 RTD or linear
DO8 Module 8 Channels, Supply: 15vdc-30Vdc, On/Off, Time Proportioning, Common 42Vac/dc system isolation
DI8 Module   8 Channel logic input with 42Vac/dc system isolation
CT3 Module 3 Channels, Current Input Range 0-50mA rms, Accuracy: ±2% of span, No isolation, Overload current: 300mA, 1 CT3 per Mini8
RL8 Module   8 Channel Form A relay (NO) max 2A @ 264Vac
AO4/AO8 Module 4 or 8 Channels, Range 0-20mA, 360R load, 42Vac/dc channel isolation
SP Programmer 8 Programmers, 16 Segments and 8 Events each, External Run, Hold, Reset, Skip Segment, Advance segment
Maths & Logic 24 x 2 Input Maths, 24 x 2 Input Logic, 4 x 8 Input logic, 4 x 8 input multiplexor, 32 User Values, 4 x 8 Multiple Input
Recipes 8 Recipes, 24 tags in each
Timer Functions 8 Timers, 2 Counters, 2 totalizers, Non-volatile real time clock
Power Supply (2500P Recommended) 17.8Vdc-28.8Vdc, Power consumption 15W max, 10W typical
Approvals EMC: EN50081-2, EN50082-2. Safety: EN61010, C-UL