Wiring Do not run input wires with power cabling.
Ground shields at one point only. Use compensating cable for thermocouple
wiring. For logic input, use an external contact with a rating >0.5 mA, 5
Vdc. Non-isolated logic outputs depend on the SSR for isolation. Relay outputs
are internally protected by a varistor. When inductive loads (such as mercury
contactors) are used, or external switches are connected in series with
internal contacts, high voltage transients may affect performance of the
instrument. In this case it is recommended to install an additional RC snubber
network across the contacts as shown. Contact Barber-Colman |
|
| Mounting: |
| Dimensions: |
48W x 48H x 122D mm |
| Cutout: |
45W x 45H mm (-0, +0.6 mm) 60 mm min.
center-to-center vertical spacing 75 mm min. center-to-center horizontal
spacing |
| Weight: |
450 gm |
|
 |
|