TECHNICAL
SPECIFICATION |
| Case: |
|
|
Polycarbonate
grey. Self-extinguishing degree V-0 according to UL, VDE and CSA. |
| Front Protection: |
|
Designed and tested for IP65 and NEMA 4X for indoor locations
(when panel gasket is installed). Tested in accordance with IEC 529, CEI 70-1
and NEMA 250-191 STD. |
| Installation: |
|
|
Panel mounting by
means of brackets. Instrument removable from case by safety screw. |
| Rear Terminal Block: |
|
|
Screw
terminals with safety rear cover. |
| Dimensions: |
|
48 x 48 mm (1.890 x 1.890 in)
according to DIN 43700; 122 mm (4.803 in) depth. |
| Weight: |
|
450 grams
maximum (1 pound). |
| Power
Supply: |
|
|
(Switch Mode) from 100 to 240
Vac, 50/60 Hz (+10% to -15% of the nominal value) or 24 Vdc/Vac, ±10% of
the nominal value). |
| Power Consumption: |
|
8 VA |
| Insulation Resistance: |
|
Less than 100 MW according to IEC 348. |
| Isolation Voltage: |
|
|
1500 Vrms
according to IEC 348. |
| D/A
Conversion: |
|
|
Dual slope integration. |
| Noise Immunity: |
|
|
- Electrical
fast transient/burst requirements: Severity Level 3 (according to IEC
801-4). |
|
|
|
- Electrical discharge
requirements: Severity Level 8 (acording to IEC 801-2). |
| Common Mode Rejection Ratio: |
|
120 dB @
50/60 Hz. |
| Normal Mode Rejection Ratio: |
|
60 dB @ 50/60 Hz. |
| Accuracy: |
|
|
±0.2%
full scale value @ 25 °C and nominal power supply voltage. |
| Operating Temperature: |
|
From 0 to 50 °C. |
| Storage Temperature: |
|
-30 to 70
°C. |
| Humidity: |
|
|
From 20 to 85% RH
non-condensing. |
| Protection: |
|
|
- WATCH DOG
for automatic reset. |
|
|
|
- DIP switches for
configuration and calibration parameter protection. |
Thermocouple Inputs |
| Type: |
|
|
J, K, L, N, R, S and T are
keyboard configurable. (All the inputs are factory calibrated and selectable by
front keyboard.) |
| Engineering Units: |
|
|
°C and
°F keyboard configurable. |
| Line
Resistance Compensation Error: |
|
Max. ±0.1% of the input
span with input impedance of 100 W. |
| Sensor Break |
|
|
Downscale or
upscale programmable. |
| Reference
Junction: |
|
|
Automatic compensation from 0
to 50 °C. |
| Reference Junction Drift: |
|
0.1
°C/°C. |
| Input
Impedance: |
|
|
Less than 100 KW. |
| Calibration: |
|
|
According to
IEC 584-1. |
RTD Input |
| RTD Input |
|
|
Pt 100 3
wire connection. |
| Calibration: |
|
|
According to DIN 43760. |
| Line Resistance: |
|
|
Max 20
W/wire with no measurable error. |
| Engineering
Units: |
|
|
°C and °F keyboard
programmable. |
| Sensor Break: |
|
|
A special
test is provided to signal OVERRANGE when input resistance is less than 15 W
(short circuit sensor detection). |
mAdc and Vdc
Inputs |
| mAdc Input (Standard): |
|
0 to 20 mAdc
and 4 to 20 mAdc, keyboard programmable. Input Impedance: less than 3
W. |
| Vdc Input: |
|
|
0 to 5 Vdc and 1 to 5 Vdc,
programmable. Input impedance greater than 90 KW. |
|
|
|
0 to 10 Vdc
and 2 to 10 Vdc, programmable. Input impedance greater than 180 KW. |
|
|
|
0 to 60 mVdc and 12 to 60
mVdc, programmable. Input impedance greater than 1 MW. |
| Readout: |
|
|
Keyboard
programmable from -1999 to 4000. |
| Decimal
Point: |
|
|
Programmable in any
position. |
Logic Input |
|
|
|
Selects between SP1/SP2.
Requires external contact with rating greater than 0.5 mA, 5 Vdc. |
Control Action |
| Algorithm: |
|
|
PID + Smart AT. |
| Type: |
|
|
One control
output. |
| Proportional
Band: |
|
|
Programmable from 1.0% to
100.0% of the input span. |
| Integral Time: |
|
|
Programmable
from 20 seconds to 20 minutes (or off). |
| Derivative
Time: |
|
|
Programmable from 1 second to
10 minutes (or off). |
| Integral Preload: |
|
|
Programmable
from 0 to 100% of the output range. |
| Out 1 Cycle
Time: |
|
|
From 1 to 200 seconds. |
| Standby/Manual Mode: |
|
Selectable
by front pushbutton. |
| Setpoint
Limiters: |
|
|
Setpoint low limit and
setpoint high limit are programmable. |
Control Outputs |
| Type: |
|
|
Time proportioning. |
| Update Time: |
|
|
250 ms. |
| Direct/Reverse Action: |
|
Keyboard programmable. |
| Cycle Time: |
|
|
Programmable
from 1 second to 99 seconds. |
| Output Level Indication: |
|
Shows percentage on the lower
display. |
| Output Status Indication: |
|
One
indicator (OUT1) lit when the output is in ON condition. |
| Output Level
Limit: |
|
|
From 0 to 100%. |
| Output Relay: |
|
|
SPST contact
with rated current 4 Amps at 250 Vac on resistive load. |
| Logic
Voltage for SSR Driver: |
|
Logic Level 0: Less than 0.5
Vdc. |
|
|
|
Logic Level
1: 24 Vdc ±20% @ 1 mA |
|
|
|
14 Vdc ±20% @ 20
mA |