Wiring Do not run input wires
with power cabling. Ground shields at one point only. Use compensating cable
for thermocouple wiring. Non-isolated logic outputs depend on the SSR for
isolation. Relay outputs are internally protected by a varistor. When inductive
loads (such as mercury contactors) are used, or external switches are connected
in series with internal contacts, high voltage transients may affect
performance of the instrument. In this case it is recommended to install an
additional RC snubber network across the contacts as shown. Contact
Barber-Colman. |
|
| Mounting |
| Dimensions: |
48W x 48H x 122D mm |
| Cutout: |
45W x 45H mm (-0, +0.6 mm) 60 mm min.
center-to-center vertical spacing 75 mm min. center-to-center horizontal
spacing |
| Weight: |
250 gm |
|

 |
|