TECHNICAL SPECIFICATION (7SF)
Case: ABS grey. Self-extinguishing degree V-0 according to UL-94.
Front Protection: Designed and tested for IP65 and NEMA 4X for indoor locations (with gasket installed).
Installation: Panel mounting by means of brackets; or DIN rail.
Rear Terminal Block: Up to 15 screw terminals, with safety rear cover.
Dimensions: 48 x 48 mm (1.890 x 1.890 in.) according to DIN 43700; 122 mm (4.803 in.) depth.
Weight: 250 grams maximum (1 pound)
Power Supply Switch Mode. 100 to 240 Vac. 50/60 Hz (+10% to -15% of the nominal value) or 24 Vac/Vdc (±10% of the nominal value).
Power Consumption: 8 VA.
Insulation Resistance: Greater than 100 MW according to IEC 348.
Isolation Voltage: 1500 Vrms according to IEC 348.
D/A Conversion: Dual slope integration.
Noise Immunity: a) Electrical fast transient/burst requirements: Severity Level 3 (according to IEC 801-4).
b) Electric discharge requirements: Severity Level 8 (according to IEC 801-2).
Sampling Time: - For linear inputs - 250 ms.
- For TC or RTD inputs - 500 ms.
Accuracy: ±0.2% full scale value @ 25 °C and nominal power supply voltage.
Common Mode Rejection Ratio:3 120 dB @ 50/60 Hz.
Normal Mode Rejection Ratio: 60 dB @ 50/60 Hz.
Operating Temperature: From 0 to 50 °C.
Storage Temperature: From -20 to 70 °C.
Humidity: From 20% to 85% RH non-condensing.
Protection: a) WATCH DOG for automatic reset.
b) DIP Switches for configuration and calibration parameters.

Inputs (All inputs are factory calibrated and selectable by front keyboard.)
Thermocouples Type: J, K, L, R, S and N are keyboard configurable.
Engineering Units: °C and °F keyboard configurable.
Sensor Break: Downscale or upscale programmable.
Reference Junction: Automatic compensation for ambient temperature between 0 and 50 °C.
Reference Junction Drift: 0.1 °C/°C.
Input Impedance: Greater than 1 MW.
Calibration: According to IEC 584-1

RTD Input
RTD Type: Pt 100 3 wire connection.
Calibration: According to DIN 43760.
Line Resistance: Max 20 W/wire with no appreciable error.
Engineering Units: °C and °F keyboard configurable.
Sensor Break: Open sensor detection and one or more open wires. Sensor short circuit detection.
Standard Ranges: °C -199.9 to 400.0 °C
-200 to 800 °C
°F -199.9 to 400.0 °F
-330 to 1470 °F
NOTE: For RTD inputs, the minimum span is 100 °C or 200 °F, which makes it possible to increase the sensitivity of the control parameters.

mAdc and Vdc Linear Inputs
mAdc Input (Standard): 0 to 20 mAdc and 4 to 20 mAdc keyboard configurable.
Input Impedance: Less than 5 W.
Vdc Input: 0 to 5 Vdc and 1 to 5 Vdc, configurable. Input impedance greater than 200 KW.
0 to 10 Vdc and 2 to 10 Vdc, configurable. Input impedance greater than 400 KW.
0 to 60 mVdc and 12 to 60 mV, configurable. Input impedance greater than 1 MW.
Read-out: Keyboard configurable from -1999 to 4000.
Decimal Point: Configurable in any position

Current Transformer Input for OUT 1 Heater Breakdown Detection
(Optional, 7SF only) This feature allows measurement of the OUT 1 load current by means of a current transformer and signals an alarm condition when the current is below a pre-programmed threshold value.
Input Range: 50 mAac.
Scaling: Configurable from 10 Amps to 100 Amps (with a 1 Amp step).
Resolution: - for full scale up to 20 Amps: 0.1 Amp.
- for full scale from 21 Amps to 100 Amps: 1 Amp.
Active Period: - for relay output: NO or NC configurable.
- for SSR output: logic level 1 or 0 configurable.
Minimum On time to perform the measurement: 50 ms.
NOTE: The heater breakdown detection feature precludes the use of logic inputs and external setpoint selection.

Logic Inputs
The 7SF is equipped with a logic input used to select between the main and auxiliary setpoint (SP or SP2). Use an external contact with a contact rating greater than 0.5 mA, 5Vdc. The instrument needs 100 ms to recognize a contact status variation.
NOTE: This function excludes the current transformer input (Output 1 heater breakdown alarm).

Setpoints
Two setpoints are available: - Main Setpoint (SP).
- Auxiliary Setpoint (SP2).
Setpoint Transfer: Transfer between SP1 and SP2 can be driven by logic input (contact closure). The transfer can be by a step or by a ramp with two different configurable rates of change (ramp up and ramp down).
Setpoint Limiters: Setpoint low limit and setpoint high limit are configurable.

Control Action
Algorithm: PID + Smart AT.
Type: One (heating) or two (heating/cooling) control outputs.
Proportional Band: Configurable
- From 1.0% to 100.0% of the input span for process with one control output.
- From 1.5% to 100% of the input span for process with two control outputs.
Setting the PB equal to zero changes the control action to ON/OFF.
Hysteresis (for ON/OFF control action): Configurable from 0.1% to 10.0% of the input span.
Integral Time: Configurable from 20 seconds to 20 minutes or excluded.
Derivative Time: Configurable from 1 second to 10 minutes or excluded.
Integral Preload: Configurable: - for 1 control output, from 0 to 100% of the output range.
- for 2 control outputs, from -100% to +100% of the heating/cooling output range.
Out 1 (heating) Cycle Time: From 1 to 200 seconds.
AUTO/MANUAL Mode: Selectable by front pushbutton or logic input.
AUTO/MANUAL Transfer: Bumpless.
Two Control Outputs (heating/cooling)
Relative Cooling Gain: Keyboard configurable from 0.20 to 1.00.
Cooling Cycle Time: From 1 to 200 seconds.
Overlap/Deadband: Keyboard configurable from -20% (deadband) to +50% (overlap) of the proportional band.
Note: By setting the proper cooling medium (air, oil or water) during configuration, the instrument will automatically set the cooling (OUT 2) parameters.

Control Outputs
Type: Time Proportioning.
Direct/Reverse Action: Keyboard configurable.
Output Level Indication: Separate displays for the Output 1 level (heating) and the Output 2 level (cooling).
Output Status Indication: Two LED indicators (OUT 1 and OUT 2) are lit when their respective output is ON.
Output Level Limiter: - For 1 control output: From 0 to 100% of the output span.
- For 2 control outputs: From -100 to 100% of the main (heating) output span.
This function may operate at instrument startup for a configurable time. To avoid thermal shock and/or preheating, it can be left active.
Relay Outputs Output Cycle Time: Configurable from 1 to 99 seconds.
Output 1: SPDT contact. The selection of the NO or NC contact is made by jumper.
Contact Rating: 3 Amps at 250 Vac on resistive load.
Output 2 (Cooling): SPST contact with rated current 2 Amps at 250 Vac on resistive load.
Logic Voltage for SSR Driver (Output 1 Only):
Logic Level 0: Vout less than 0.5 Vdc.
Logic Level 1: 14 Vdc ±20% @ 17 mA max.
24 Vdc ±20% @ 1 mA max.
Output Safety Value: When the instrument detects an out of range or a sensor break condition, it can force the output to a configurable safety value.

Output “Turn Off” Function
This function disables the control output allowing the instrument to operate as an indicator. When control is resumed, “turn off” is disabled and the instrument will operate as follows: the integral component of the output signal will be set to zero, the soft start function will be enabled, and the alarm masking function will be enabled.

Alarms
This instrument is equipped with two independent outputs configurable as:
- Heating + Alarm 1
- Heating + Cooling
An optional output is available as Alarm 2 or the heater breakdown alarm output.
Output Action: Direct or reverse function configurable.
Alarm Functions: Each alarm can be configured as process alarm, band alarm or deviation alarm.
Alarm Reset: Automatic or manual reset programmable on each alarm.
Alarm Masking: Each alarm can be configured as masked alarm or standard alarm. Alarm masking allows suppression of alarm indicators at startup and after a setpoint change.
Alarm Indication: Two indicators show when the respective alarm is ON.
Alarm Outputs: Two SPST relays. Contact rated at 2 Amps, 250 Vac on resistive load.
Process Alarm Operating Mode: High or low configurable.
Alarm Setpoint: Configurable in engineering units within the entire range.
Hysteresis: Configurable from 0.1% to 10.0% of the input span.
Band Alarm Operating Mode: Inside or outside band configurable.
Alarm Setpoint: Configurable from 0 to 500 units.
Hysteresis: Configurable from 0.1% to 10.0% of the input span.
Deviation Alarm Operating Mode: High or low configurable.
Alarm Setpoint: Configurable from -500 to +500 units.
Hysteresis: Configurable from 0.1% to 10.0% of the input span.
Heater Breakdown Alarm (Can be used only for instruments with heater breakdown input option.)
Operating Mode: Low alarm.
Alarm Setpoint: Configurable in engineering units within the readout span.

Serial Interface (Optional)
Type: RS-485.
Protocol Type: MODBUS, JBUS, or Barber-Colman proprietary polling/selecting.
Baud Rate: Keyboard configurable from 600 to 19200 BAUD.
Byte Format: 7 or 8 bit configurable.
Parity: Even, odd or none configurable.
Stop Bit: One.
Address: - From 1 to 31 for Barber-Colman protocol.
- From 1 to 255 for all other protocols.
Output Voltage Levels: According to EIA standard.
Last updated January 9, 2004