Wiring Do not run input wires with power cabling.
Ground shields at one point only. Use compensating cable for thermocouple
wiring. Non-isolated logic outputs depend on the SSR for isolation. The OP1 and
OP2 relays are internally protected by a varistor. When inductive loads (such
as mercury contactors) are used, or external switches are connected in series
with internal contacts, high voltage transients may affect performance of the
instrument. In this case it is recommended to install an additional RC snubber
network across the contacts as shown. Contact Barber-Colman. |
 |
|
Mounting |
|
| Dimensions: |
48W x 48H x 100D mm |
| Cutout: |
45W x 45H mm (-0, +0.6 mm) 60 mm
min. center-to-center vertical spacing 75 mm min. center-to-center
horizontal spacing |
| Weight: |
160 gm |
 |
|