TECHNICAL
SPECIFICATION |
| Case: |
|
|
Polycarbonate in
dark grey. Self-extinguishing degree V-0 according to UL-94. |
| Front Protection: |
|
Designed and tested for IP65 and NEMA 4X for indoor locations
(when panel gasket is installed). |
| Installation: |
|
|
Panel
mounting. |
| Rear Terminal Block: |
|
|
Ten screw
terminals with safety rear cover. |
| Dimensions: |
|
48 x 48 mm (1.890 x 1.890 in.)
according to DIN 43700; 100 mm (3.937 in.) depth. |
| Cutout: |
|
45 x 45 mm
-0 mm, +0.6 mm. (1.772 x 1.772 in. -0 in, +0.024) |
| Weight: |
|
|
160 grams (6.6 ounces). |
| Power Supply: |
|
|
From 100 to
240 Vac, 50/60 Hz, or 24 Vac/Vdc. |
| Power
Supply Variation: |
|
-15% to +10% of nominal
value. |
| Power Consumption: |
|
|
5 VA. |
| Insulation Resistance: |
|
Less than 100 MW (Class III apparatus) according to IEC 348. |
| Isolation Voltage: |
|
|
1500
Vrms. |
| D/A
Conversion: |
|
|
Dual slope integration. |
| Noise Immunity: |
|
|
a)
Electrical fast transient/burst requirements: Severity Level 3 (according to
IEC 801-4). |
|
|
|
b) Electrical discharge
requirements: Severity Level 8 (according to IEC 801-2). |
| Sampling Time: |
|
|
500 ms
typical. |
| Accuracy: |
|
|
±0.3% full scale value
±1 digit @ 25 °C and nominal power supply value. |
| Temperature Drift: |
|
|
Less than
200 ppm/°C of full scale value selected (RJ excluded). |
|
|
|
Less than 400 ppm/°C of
full scale value for RTD range -19.9 to 99.99. |
| Reference Junction Drift: |
|
0.1
°C/°C. |
| Common Mode Rejection Ratio: |
|
120 dB @ 50/60 Hz. |
| Normal Mode Rejection Ratio: |
|
60 dB @
50/60 Hz. |
| Operating Temperature: |
|
0 to 50 °C. |
| Storage Temperature: |
|
-30 to 70
°C. |
| Humidity: |
|
|
From 20% to 85% RH
non-condensing. |
Control Actions |
| On/Off, PID or
Smart AT Autotuning |
|
| Special Function: |
|
|
Standby
alarm sequence. |
| Protection: |
|
|
Internal jumper for
calibration and configuration parameter protection. |
Inputs (All inputs are
factory calibrated and selectable by front keyboard.) |
| Input: |
|
|
Thermocouples (J, L, K, N) or
RTD Pt 100. Input types are keyboard programmable. |
| Engineering Units: |
|
|
°C or
°F configurable. |
| Reference
Junction: |
|
|
Automatic compensation from 0
to 50 °C. |
| Line Impedance: |
|
|
100W max for TC input. |
|
|
|
Less than 4W per wire for RTD input. |
| Sensor Break: |
|
|
Downscale or
upscale programmable. On RTD input, a special test is provided to signal
OVERRANGE when input resistance is less than 15W.
(Short circuit sensor detection.) |
| Calibration: |
|
|
According to IEC 584-1 and DIN
43710-1977. |
Outputs |
| Main Output: |
|
|
a) Relay SPDT, contact rating
3 Amps @ 250 Vac on resistive load. |
|
|
|
b) Logic
output for SSR, 700 W maximum load, short circuit
protected. |
|
Logic Level
1: |
|
14 Vdc ±20% @ 20 mA
max |
|
|
|
24 Vdc max
±20% @ 1 mA |
|
Logic Level
0: |
|
Less than 0.5 Vdc |
| Cooling Output (7SH only) |
|
a) Relay
SPST and contact normally open, contact rating 1 Amp @ 250 Vac on resistive
load. |
|
|
|
b) Logic output for SSR, 700
W maximum load, short circuit protected. |
|
Logic Level 1: |
|
14 Vdc
±20% @ 20 mA max |
|
|
|
24 Vdc max ±20% @ 1
mA |
|
Logic Level 0: |
|
Less than
0.5 Vdc |
Alarm |
| Alarm Functions: |
|
|
Process
Alarm |
|
|
|
Deviation Alarm |
|
|
|
Band
Alarm |
|
|
|
Instrument Malfunctioning
Annunciator |
| Type of Alarm: |
|
|
- High/Low
(Outside/Inside for band alarm) |
|
|
|
- Direct/Reverse |
|
|
|
- Standby
Sequence/No Standby Sequence |
| Alarm
Hysteresis: |
|
|
0.1 to 10.0% of input span or
1 least significant digit. |
| Alarm Output: |
|
|
Relay SPST 1
Amp @ 250 Vac resistive load. |
7SD
Characteristics |
| Display: |
|
|
3 digit 7
segment LED display; 10 mm high. |
| Bargraph: |
|
|
1 green LED + 2 red LEDs for 5
level deviation indication. |
| Indicators: |
|
|
1 red LED
when heating output is ON. |
|
|
|
1 red LED when Alarm 1 is
ON. |
|
|
|
1 green LED
when Smart AT is enabled. |
| Upper
Display: |
|
|
3 digit 7 segment LED display;
10 mm high. |
| Lower Display: |
|
|
3 digit 7
segment LED display; 7.6 mm high. |
| Indicators: |
|
|
1 red LED when heating output
is ON. |
|
|
|
1 red LED
when cooling output is ON or alarm is ON. |
|
|
|
1 green LED when Smart AT is
enabled. |
| Cooling Output (7SH only): |
|
a) Relay
SPST and contact normal open, contact rating 1 Amp @ 250 Vac on resistive
load. |
|
|
|
b) Logic output for SSR 700 W
maximum load, short circuit protected. |
|
Logic Level 1: |
|
14 Vdc
±20% @ 20 mA max |
|
|
|
24 Vdc max ±20% @ 1
mA |
|
Logic Level 0: |
|
Less than
0.5 Vdc |