TECHNICAL SPECIFICATION
Case: Polycarbonate in dark grey. Self-extinguishing degree V-0 according to UL-94.
Front Protection: Designed and tested for IP65 and NEMA 4X for indoor locations (when panel gasket is installed).
Installation: Panel mounting.
Rear Terminal Block: Ten screw terminals with safety rear cover.
Dimensions: 48 x 48 mm (1.890 x 1.890 in.) according to DIN 43700; 100 mm (3.937 in.) depth.
Cutout: 45 x 45 mm -0 mm, +0.6 mm. (1.772 x 1.772 in. -0 in, +0.024)
Weight: 160 grams (6.6 ounces).
Power Supply: From 100 to 240 Vac, 50/60 Hz, or 24 Vac/Vdc.
Power Supply Variation: -15% to +10% of nominal value.
Power Consumption: 5 VA.
Insulation Resistance: Less than 100 MW (Class III apparatus) according to IEC 348.
Isolation Voltage: 1500 Vrms.
D/A Conversion: Dual slope integration.
Noise Immunity: a) Electrical fast transient/burst requirements: Severity Level 3 (according to IEC 801-4).
b) Electrical discharge requirements: Severity Level 8 (according to IEC 801-2).
Sampling Time: 500 ms typical.
Accuracy: ±0.3% full scale value ±1 digit @ 25 °C and nominal power supply value.
Temperature Drift: Less than 200 ppm/°C of full scale value selected (RJ excluded).
Less than 400 ppm/°C of full scale value for RTD range -19.9 to 99.99.
Reference Junction Drift: 0.1 °C/°C.
Common Mode Rejection Ratio: 120 dB @ 50/60 Hz.
Normal Mode Rejection Ratio: 60 dB @ 50/60 Hz.
Operating Temperature: 0 to 50 °C.
Storage Temperature: -30 to 70 °C.
Humidity: From 20% to 85% RH non-condensing.

Control Actions
On/Off, PID or Smart AT Autotuning
Special Function: Standby alarm sequence.
Protection: Internal jumper for calibration and configuration parameter protection.

Inputs (All inputs are factory calibrated and selectable by front keyboard.)
Input: Thermocouples (J, L, K, N) or RTD Pt 100. Input types are keyboard programmable.
Engineering Units: °C or °F configurable.
Reference Junction: Automatic compensation from 0 to 50 °C.
Line Impedance: 100W max for TC input.
Less than 4W per wire for RTD input.
Sensor Break: Downscale or upscale programmable. On RTD input, a special test is provided to signal OVERRANGE when input resistance is less than 15W. (Short circuit sensor detection.)
Calibration: According to IEC 584-1 and DIN 43710-1977.

Outputs
Main Output: a) Relay SPDT, contact rating 3 Amps @ 250 Vac on resistive load.
b) Logic output for SSR, 700 W maximum load, short circuit protected.
Logic Level 1: 14 Vdc ±20% @ 20 mA max
24 Vdc max ±20% @ 1 mA
Logic Level 0: Less than 0.5 Vdc
Cooling Output (7SH only) a) Relay SPST and contact normally open, contact rating 1 Amp @ 250 Vac on resistive load.
b) Logic output for SSR, 700 W maximum load, short circuit protected.
Logic Level 1: 14 Vdc ±20% @ 20 mA max
24 Vdc max ±20% @ 1 mA
Logic Level 0: Less than 0.5 Vdc

Alarm
Alarm Functions: Process Alarm
Deviation Alarm
Band Alarm
Instrument Malfunctioning Annunciator
Type of Alarm: - High/Low (Outside/Inside for band alarm)
- Direct/Reverse
- Standby Sequence/No Standby Sequence
Alarm Hysteresis: 0.1 to 10.0% of input span or 1 least significant digit.
Alarm Output: Relay SPST 1 Amp @ 250 Vac resistive load.

7SD Characteristics
Display: 3 digit 7 segment LED display; 10 mm high.
Bargraph: 1 green LED + 2 red LEDs for 5 level deviation indication.
Indicators: 1 red LED when heating output is ON.
1 red LED when Alarm 1 is ON.
1 green LED when Smart AT is enabled.
Upper Display: 3 digit 7 segment LED display; 10 mm high.
Lower Display: 3 digit 7 segment LED display; 7.6 mm high.
Indicators: 1 red LED when heating output is ON.
1 red LED when cooling output is ON or alarm is ON.
1 green LED when Smart AT is enabled.
Cooling Output (7SH only): a) Relay SPST and contact normal open, contact rating 1 Amp @ 250 Vac on resistive load.
b) Logic output for SSR 700 W maximum load, short circuit protected.
Logic Level 1: 14 Vdc ±20% @ 20 mA max
24 Vdc max ±20% @ 1 mA
Logic Level 0: Less than 0.5 Vdc