TECHNICAL SPECIFICATION (7SC) |
| Case: |
|
|
ABS grey.
Self-extinguishing degree V-0 according to UL-94. |
| Front Protection: |
|
Designed and tested for IP65 and NEMA 4X for indoor locations
(with gasket installed). |
| Installation: |
|
|
Panel mounting by
means of brackets; or DIN rail. |
| Rear Terminal Block: |
|
|
Up to 15
screw terminals, with safety rear cover. |
| Dimensions: |
|
48 x 48 mm (1.890 x 1.890 in.)
according to DIN 43700; 122 mm (4.803 in.) depth. |
| Weight: |
|
250 grams
maximum (1 pound) |
| Power Supply |
|
|
Switch Mode. 100 to 240 Vac.
50/60 Hz (+10% to -15% of the nominal value) or 24 Vac/Vdc (±10% of the
nominal value). |
| Power Consumption: |
|
|
8 VA. |
| Insulation Resistance: |
|
Greater than 100 MW according to IEC 348. |
| Isolation Voltage: |
|
|
1500 Vrms
according to IEC 348. |
| D/A
Conversion: |
|
|
Dual slope integration. |
| Noise Immunity: |
a) |
|
Electrical
fast transient/burst requirements: Severity Level 3 (according to IEC
801-4). |
|
b) |
|
Electric discharge
requirements: Severity Level 8 (according to IEC 801-2). |
| Sampling Time: |
|
|
- For linear
inputs - 250 ms. |
|
|
|
- For TC or RTD inputs - 500
ms. |
| Accuracy: |
|
|
±0.2%
full scale value @ 25 °C and nominal power supply voltage. |
| Common Mode Rejection Ratio:3 |
|
120 dB @ 50/60 Hz. |
| Normal Mode Rejection Ratio: |
|
60 dB @
50/60 Hz. |
| Operating Temperature: |
|
From 0 to 50 °C. |
| Storage Temperature: |
|
From -20 to
70 °C. |
| Humidity: |
|
|
From 20% to 85% RH
non-condensing. |
| Protection: |
a) |
|
WATCH DOG
for automatic reset. |
|
b) |
|
DIP Switches for configuration
and calibration parameters. |
Inputs (All inputs are
factory calibrated and selectable by front keyboard.) |
| Thermocouples
Type: |
|
|
J, K, L, R, S and N are
keyboard configurable. |
| Engineering Units: |
|
|
°C and
°F keyboard configurable. |
| Sensor
Break: |
|
|
Downscale or upscale
programmable. |
| Reference Junction: |
|
|
Automatic
compensation for ambient temperature between 0 and 50 °C. |
| Reference Junction Drift: |
|
0.1 °C/°C. |
| Input Impedance: |
|
|
Greater than
1 MW. |
| Calibration: |
|
|
According to IEC 584-1 |
RTD Input |
| RTD Type: |
|
|
Pt 100 3 wire connection. |
| Calibration: |
|
|
According to
DIN 43760. |
| Line
Resistance: |
|
|
Max 20 W/wire with no appreciable error. |
| Engineering Units: |
|
|
°C and
°F keyboard configurable. |
| Sensor
Break: |
|
|
Open sensor detection and one
or more open wires. Sensor short circuit detection. |
| Standard Ranges: |
°C |
|
-199.9 to
400.0 °C |
|
|
|
-200 to 800 °C |
|
°F |
|
-199.9 to
400.0 °F |
|
|
|
-330 to 1470 °F |
| NOTE: |
|
|
For RTD
inputs, the minimum span is 100 °C or 200 °F, which makes it possible
to increase the sensitivity of the control parameters. |
mAdc
and Vdc Linear Inputs |
| mAdc Input (Standard): |
|
0 to 20 mAdc
and 4 to 20 mAdc keyboard configurable. |
| Input
Impedance: |
|
|
Less than 5
W. |
| Vdc Input: |
|
|
0 to 5 Vdc
and 1 to 5 Vdc, configurable. Input impedance greater than 200 KW. |
|
|
|
0 to 10 Vdc and 2 to 10 Vdc,
configurable. Input impedance greater than 400 KW. |
|
|
|
0 to 60 mVdc
and 12 to 60 mV, configurable. Input impedance greater than 1 MW. |
| Read-out: |
|
|
Keyboard configurable from
-1999 to 4000. |
| Decimal Point: |
|
|
Configurable
in any position |
Current Transformer Input for OUT 1 Heater Breakdown Detection |
| (Optional, 7SF only) |
|
|
This feature
allows measurement of the OUT 1 load current by means of a current transformer
and signals an alarm condition when the current is below a pre-programmed
threshold value. |
| Input Range: |
|
|
50 mAac. |
| Scaling: |
|
|
Configurable
from 10 Amps to 100 Amps (with a 1 Amp step). |
| Resolution: |
|
|
- for full scale up to 20
Amps: 0.1 Amp. |
|
|
|
- for full
scale from 21 Amps to 100 Amps: 1 Amp. |
| Active
Period: |
|
|
- for relay output: NO or NC
configurable. |
|
|
|
- for SSR
output: logic level 1 or 0 configurable. |
| Minimum On time to perform the measurement: |
|
50 ms. |
| NOTE: |
|
|
The heater
breakdown detection feature precludes the use of logic inputs and external
setpoint selection. |
Logic
Inputs |
| The 7SF is equipped with a logic input used to select between
the main and auxiliary setpoint (SP or SP2). Use an external contact with a
contact rating greater than 0.5 mA, 5Vdc. The instrument needs 100 ms to
recognize a contact status variation. |
| NOTE: |
|
|
This function excludes the
current transformer input (Output 1 heater breakdown alarm). |
Setpoints |
| Two
setpoints are available: |
|
- Main Setpoint (SP). |
|
|
|
- Auxiliary
Setpoint (SP2). |
| Setpoint
Transfer: |
|
|
Transfer between SP1 and SP2
can be driven by logic input (contact closure). The transfer can be by a step
or by a ramp with two different configurable rates of change (ramp up and ramp
down). |
| Setpoint Limiters: |
|
|
Setpoint low
limit and setpoint high limit are configurable. |
Control Action |
| Algorithm: |
|
|
PID + Smart
AT. |
| Type: |
|
|
One (heating) or two
(heating/cooling) control outputs. |
| Proportional Band: |
|
|
Configurable |
|
|
|
- From 1.0% to 100.0% of the
input span for process with one control output. |
|
|
|
- From 1.5%
to 100% of the input span for process with two control outputs. |
|
|
|
Setting the PB equal to zero
changes the control action to ON/OFF. |
| Hysteresis (for ON/OFF control action): |
|
Configurable
from 0.1% to 10.0% of the input span. |
| Integral
Time: |
|
|
Configurable from 20 seconds
to 20 minutes or excluded. |
| Derivative Time: |
|
|
Configurable
from 1 second to 10 minutes or excluded. |
| Integral
Preload: |
Configurable: |
|
- for 1 control output, from 0
to 100% of the output range. |
|
|
|
- for 2
control outputs, from -100% to +100% of the heating/cooling output range. |
| Out 1
(heating) Cycle Time: |
|
From 1 to 200 seconds. |
| AUTO/MANUAL Mode: |
|
|
Selectable
by front pushbutton or logic input. |
| AUTO/MANUAL Transfer: |
|
Bumpless. |
| Two Control Outputs (heating/cooling) |
|
|
| Relative Cooling Gain: |
|
Keyboard configurable from
0.20 to 1.00. |
| Cooling Cycle Time: |
|
|
From 1 to
200 seconds. |
| Overlap/Deadband: |
|
|
Keyboard configurable from
-20% (deadband) to +50% (overlap) of the proportional band. |
| Note: |
|
|
By setting
the proper cooling medium (air, oil or water) during configuration, the
instrument will automatically set the cooling (OUT 2) parameters. |
Control Outputs |
| Type: |
|
|
Time
Proportioning. |
| Direct/Reverse Action: |
|
Keyboard configurable. |
| Output Level Indication: |
|
Separate
displays for the Output 1 level (heating) and the Output 2 level
(cooling). |
| Output Status Indication: |
|
Two LED indicators (OUT 1 and
OUT 2) are lit when their respective output is ON. |
| Output Level Limiter: |
|
|
- For 1
control output: From 0 to 100% of the output span. |
|
|
|
- For 2 control outputs: From
-100 to 100% of the main (heating) output span. |
|
|
|
This
function may operate at instrument startup for a configurable time. To avoid
thermal shock and/or preheating, it can be left active. |
| Relay
Outputs Output Cycle Time: |
|
Configurable from 1 to 99
seconds. |
| Output 1: |
|
|
SPDT
contact. The selection of the NO or NC contact is made by jumper. |
| Contact
Rating: |
|
|
3 Amps at 250 Vac on resistive
load. |
| Output 2 (Cooling): |
|
|
SPST contact
with rated current 2 Amps at 250 Vac on resistive load. |
| Logic
Voltage for SSR Driver (Output 1 Only): |
|
|
|
Logic Level 0: |
|
Vout less
than 0.5 Vdc. |
|
Logic Level 1: |
|
14 Vdc ±20% @ 17 mA
max. |
|
|
|
24 Vdc
±20% @ 1 mA max. |
| Output Safety
Value: |
|
|
When the instrument detects an
out of range or a sensor break condition, it can force the output to a
configurable safety value. |
Output Turn Off Function |
| This
function disables the control output allowing the instrument to operate as an
indicator. When control is resumed, turn off is disabled and the
instrument will operate as follows: the integral component of the output signal
will be set to zero, the soft start function will be enabled, and the alarm
masking function will be enabled. |
Alarms |
| This
instrument is equipped with two independent outputs configurable as: |
|
|
|
- Heating + Alarm 1 |
|
|
|
- Heating +
Cooling |
| An
optional output is available as Alarm 2 or the heater breakdown alarm
output. |
| Output Action: |
|
|
Direct or
reverse function configurable. |
| Alarm
Functions: |
|
|
Each alarm can be configured
as process alarm, band alarm or deviation alarm. |
| Alarm Reset: |
|
|
Automatic or
manual reset programmable on each alarm. |
| Alarm
Masking: |
|
|
Each alarm can be configured
as masked alarm or standard alarm. Alarm masking allows suppression of alarm
indicators at startup and after a setpoint change. |
| Alarm Indication: |
|
|
Two
indicators show when the respective alarm is ON. |
| Alarm
Outputs: |
|
|
Two SPST relays. Contact rated
at 2 Amps, 250 Vac on resistive load. |
| Process Alarm Operating Mode: |
|
High or low
configurable. |
| Alarm
Setpoint: |
|
|
Configurable in engineering
units within the entire range. |
| Hysteresis: |
|
|
Configurable
from 0.1% to 10.0% of the input span. |
| Band
Alarm Operating Mode: |
|
Inside or outside band
configurable. |
| Alarm Setpoint: |
|
|
Configurable
from 0 to 500 units. |
| Hysteresis: |
|
|
Configurable from 0.1% to
10.0% of the input span. |
| Deviation Alarm Operating Mode: |
|
High or low
configurable. |
| Alarm
Setpoint: |
|
|
Configurable from -500 to +500
units. |
| Hysteresis: |
|
|
Configurable
from 0.1% to 10.0% of the input span. |
| Heater Breakdown Alarm |
|
(Can be used only for
instruments with heater breakdown input option.) |
| Operating Mode: |
|
|
Low
alarm. |
| Alarm
Setpoint: |
|
|
Configurable in engineering
units within the readout span. |
Serial Interface (Optional) |
| Type: |
|
|
RS-485. |
| Protocol Type: |
|
|
MODBUS,
JBUS, or Barber-Colman proprietary polling/selecting. |
| Baud Rate: |
|
|
Keyboard configurable from 600
to 19200 BAUD. |
| Byte Format: |
|
|
7 or 8 bit
configurable. |
| Parity: |
|
|
Even, odd or none
configurable. |
| Stop Bit: |
|
|
One. |
| Address: |
|
|
- From 1 to 31 for
Barber-Colman protocol. |
|
|
|
- From 1 to
255 for all other protocols. |
| Output Voltage Levels: |
|
According to EIA
standard. |
Output 1 |
| Type: |
|
|
Opto-isolated 0-20 mA or 4-20
mA configurable. |
| Function: |
Programmable as: |
|
- control
output (heating or cooling). |
|
|
|
- retransmission of the
measured value. |
|
|
|
-
retransmission of the operating setpoint. |
| Scaling: |
|
|
Configurable from -1999 to
9999. |
| Maximum Load: |
|
|
500
W. |
| Resolution: |
|
|
- 0.1% when used as control
output. |
|
|
|
- 0.05% when
used as analog retransmission. |
| Digital
Filter: |
|
|
A digital filter for the
retran out is available (with the same time constant as the readout). |
| Output Level Indication (as control output only): |
|
From 0.0 to
100.0%. |
| Output Status Indication: |
|
The OUT 1 indicator flashes
with a duty cycle proportional to the output level. |
Output 2 |
| Type: |
|
|
SPST relay contact (NO or NC
selectable by jumper) with rated current 2 Amps at 250 Vac on resistive
load. |
| Function: |
Configurable as: |
|
- Control
output (heating or cooling). |
|
|
|
- Alarm 1 output. |
Output 3 |
| Type: |
|
|
Relay with SPST contact with
rated current 2 Amps at 250 Vac on resistive load. |
| Function: |
Configurable as: |
|
- Control
output (heating or cooling). |
|
|
|
- Alarm 2 output. |
Power Consumption |
| 10
VA. For details, refer to the relay output model numbers. |
Inputs |
| This
instrument is equipped with universal input capable of measuring 7 TC Types,
RTD, mA, mV and Volt signals. The only difference between the 7SF model and the
7SC is the addition of the TC Type T with the following ranges: |
|
TC Type: |
|
T |
|
Ranges: |
|
0 to 400.0°C |
|
|
|
0 to
750°F |
Control Action |
| Proportional Band: |
|
|
Configurable
from 1.0% to 200.0% of the input span. Setting a PB equal to zero sets the
control action to ON/OFF. |
| Integral
Time: |
|
|
Configurable from 1 second to
20 minutes (or off). |
| NOTE: |
|
|
The Heater
Breakdown Alarm is not available in the 7SC. |
Noise
Immunity |
| This instrument conforms to EEC 89/336 directive regarding
electromagnetic compatibility. |
| Emission: |
|
|
Generic emission standard EN
50081-2 |
|
|
|
Basic
emission standard EN 55011 |
| Immunity: |
|
|
Generic immunity standard EN
50082-2, Basic immunity standard: |
|
|
|
a.
Electrical discharge requirements: Severity Level 3 (according to IEC
801-2). |
|
|
|
b. Electrical fast
transient/burst requirements: Severity Level 3 (according to IEC 801-2). |
|
|
|
c. Radiated
electromagnetic field immunity between 27 MHz - 500 MHz, 10 V/m (according to
IEC 801-3). |