Control Modes: |
|
PID with Smart AT Autotuning |
| Supply Voltage: |
|
100-240 Vac (+10%, -15%), 50/60 Hz |
| Operating Ambient: |
|
0-50°C, 20-85% RH non-condensing |
| Inputs: |
|
T/C Types J, K, L, N, R, S and T(°C,
°F); |
|
|
Pt 100 3W RTD (°C, °F); Ranges: mAdc,
mVdc, Vdc |
| Feedback Potentiometer
Input: |
Non-isolated 24 Vdc (±10%) rated at 25
mAdc, |
|
|
short circuit protected |
| Logic Inputs (3): |
|
for setpoint select (SP, SP2),
Auto/Man or Rev/Dir and Local/Remote. Requires contact rated at 0.5 mA, 5 Vdc
min. |
| Output Ratings: |
|
|
|
Output 1: |
Relay, 3A/250V, SPST, NO, Resistive
|
|
|
Actuator Output linked to OP2 (Open/Close)
or |
|
|
Time Proportioning (Heat) |
|
Output 2: |
Relay, 3A/250V, SPST, NO, Resistive |
|
|
Actuator Output linked to OP1 (Open/Close) or
|
|
|
Time Proportioning (Cool) or Alarm 1 |
|
Output 3: |
Relay, 2A/250V, SPST, NO, Resistive; |
|
|
Alarm 2 and Alarm 3 (Logically OR'ed) |
| Mounting: |
|
Panel Mount or DIN Rail |