Wiring Do not run input wires with power cabling. Ground
shields at one point only. Use compensating cable for thermocouple wiring.
Non-isolated logic outputs depend on the SSR for isolation. Relay outputs are
internally protected by a varistor. When inductive loads (such as mercury
contactors) are used, or external switches are connected in series with
internal contacts, high voltage transients may affect performance of the
instrument. In this case it is recommended to install an additional RC snubber
network across the contacts as shown. Contact Barber-Colman |
 |
|
Mounting |
|
| Dimensions: |
48W x 96H x 89D mm |
| Cutout: |
45W (-0, +0.6) x 92H (-0, +0.8) mm
125 mm min. center-to-center vertical spacing 60 mm min.
center-to-center horizontal spacing |
| Weight: |
400 gm max. |
 |
|