TECHNICAL SPECIFICATION (7EF/7HF) |
| Case: |
|
|
ABS black.
Self-extinguishing degree V-0 according to UL,VDE and CSA. |
| Front Protection: |
|
Designed and tested for IP65 and NEMA 4X for indoor locations
(when panel gasket is installed). |
| Installation: |
|
|
Panel mounting by
means of brackets. |
| Rear Terminal Block: |
|
|
Up to 21
screw terminals, with safety rear cover. |
| Dimensions: |
|
48 x 96 mm (1.890 x 3.780 in.)
according to DIN 43700; 116 mm (4.567 in.) deep. |
| Weight: |
|
400 grams
maximum (1 pound). |
| Power
Supply (Switch Mode): |
|
100 to 240 Vac, 50/60 Hz (10%
to -15% of the nominal value). |
| Power Consumption: |
|
|
11 VA. |
| Insulation Resistance: |
|
Greater than 100 MW according to IEC 348. |
| Isolation Voltage: |
|
1500 Vrms
according to IEC 348. |
| D/A
Conversion: |
|
|
Dual slope integration. |
| Noise Immunity: |
a) |
|
Electrical
fast transient/burst requirements: Severity Level 3 (according to IEC
801-4). |
|
b) |
|
Electric discharge
requirements: Severity Level 8 (according to IEC 801-2). |
| Sampling Time: |
|
|
250 ms for
linear inputs. |
|
|
|
500 ms for TC or RTD
inputs. |
| Accuracy: |
|
|
±0.2%
full scale value @ 25°C and nominal power supply voltage. |
| Common Mode Rejection Ratio: |
|
120 dB @ 50/60 Hz. |
| Normal Mode Rejection Ratio: |
|
60 dB @
50/60 Hz. |
| Operating Temperature: |
|
From 0 to 50°C. |
| Storage Temperature: |
|
From -20 to
70°C. |
| Humidity: |
|
|
From 20% to 85% RH
non-condensing. |
| Protection: |
a) |
|
Watch dog
for automatic reset. |
|
b)
|
|
DIP Switches for configuration
and calibration parameters. |
Inputs (All inputs are factory calibrated and selectable from the
keyboard.) |
| Thermocouple
Types: |
|
|
J, K, L, R, S and N are
keyboard configurable. |
| Engineering Units: |
|
|
°C and
°F keyboard configurable. |
| Sensor
Break: |
|
|
Downscale or upscale
programmable. On RTD inputs, an OVERRANGE is indicated when input resistance is
less than 15 W (short circuit sensor
detection.) |
| Reference Junction: |
|
|
Automatic
compensation for an ambient temperature between 0 and 50 °C. |
| Reference Junction Drift: |
|
0.1 °C/°C. |
| Input Impedance: |
|
|
Greater than
1 MW. |
| Calibration: |
|
|
According to IEC 584-1. |
RTD Input |
| RTD Type: |
|
|
Pt 100 3 wire connection. |
| Calibration: |
|
|
According to
DIN 43760. |
| Line
Resistance: |
|
|
Maximum of 20
W/wire with no appreciable error. |
| Engineering Units: |
|
|
°C and
°F keyboard configurable. |
| Sensor Break Detection: |
|
Open sensor (one or more open
wires), and short circuit sensor detection. |
mAdc and Vdc Linear Inputs |
| mAdc
Input (Standard): |
|
0 to 20 mAdc and 4 to 20 mAdc
keyboard configurable. |
| Input Impedance: |
|
|
Less than 5
W. |
| Vdc Input: |
|
|
0 to 5 Vdc and 1 to 5 Vdc,
configurable. Input impedance greater than 200 KW. |
|
|
|
0 to 10 Vdc
and 2 to 10 Vdc configurable. Input impedance greater than 400 KW. |
|
|
|
0 to 60 mVdc and 12 to 60 mV
configurable. Input impedance greater than 1 MW. |
| Readout: |
|
|
Keyboard
configurable from -1999 to 4000. |
| Decimal
Point: |
|
|
Configurable to any
position. |
Current Transformer Input for OUT 1 Heater Breakdown Detection |
| (Optional, 7EF/7HF only) |
|
This feature allows
measurement of the load current by means of a current transformer and signals
an alarm condition when the current is below a pre-programmed threshold
value. |
| Input Range: |
|
|
50
mAac. |
| Scaling: |
|
|
Configurable from 10 Amps to
100 Amps (with a 1 Amp step). |
| Resolution: |
|
|
- for full
scale up to 20 Amps: 0.1 Amp. |
|
|
|
- for full scale from 21 Amps
to 100 Amps: 1 Amp. |
| Active Period: |
|
|
- for relay
output: NO or NC configurable. |
|
|
|
- for SSR output: logic level
1 or 0 configurable. |
| Minimum On Time to Perform the measurement: |
|
50 ms. |
Logic Input |
| The 7EF/7HF is equipped with a logic input to select between
the main and auxiliary setpoint (SP or SP2). |
Setpoints |
| Two setpoints available: |
|
- Main
Setpoint (SP). |
|
|
|
- Auxiliary Setpoint
(SP2). |
| Setpoint Transfer: |
|
|
Transfer
between SP and SP2 by logic input (contact closure). Transfer can be either by
a step or by a ramp with two different configurable rates of change (ramp up
and ramp down). |
| Setpoint
Limits: |
|
|
Setpoint low limit and
setpoint high limit are configurable. |
Control Action |
| Algorithm: |
|
|
PID - Smart AT. |
| Type: |
|
|
One
(heating) or two (heating/cooling) control outputs. |
| Proportional
Band: |
Configurable |
|
- From 1.0% to 100.0% of the
input span for a process with one control output. |
|
|
|
- From 1.5%
to 100.0% of the input span for a process with two control outputs. |
|
|
|
Setting the PB equal to 0
changes the control action to ON/OFF. |
| Hysteresis (for ON/OFF control action): |
|
Configurable
from 0.1% to 10.0% of the input span. |
| Integral
Time: |
|
|
Configurable from 20 seconds
to 20 minutes (or off). |
| Derivative Time: |
|
|
Configurable
from 1 second to 10 minutes (or off). |
| Integral
Preload: |
Configurable: |
|
- for 1 control output, from 0
to 100% of the output range. |
|
|
|
- for 2
control outputs, from -100% to 100% of the heating/cooling output range. |
| Out 1
(heating) Cycle Time: |
|
From 1 to 200 seconds. |
| AUTO/MANUAL Mode: |
|
|
Selectable
by front pushbutton. |
| AUTO/MANUAL Transfer: |
|
Bumpless. |
| Two Control Outputs (Heating/Cooling) |
|
|
| Relative Cooling Gain: |
|
Keyboard configurable from
0.20 to 1.00. |
| Cooling Cycle Time: |
|
|
From 1 to
200 seconds. |
| Overlap/Deadband: |
|
|
Keyboard configurable from
-20% (deadband) to 50% (overlap) of the PB. |
| NOTE: |
|
|
By setting
the proper cooling medium (air, oil or water) during configuration, the
instrument will automatically set the cooling (OUT 2) parameters. |
Control
Outputs |
| Type: |
|
|
Time
Proportioning. |
| Direct/Reverse Action: |
|
Keyboard configurable. |
| Output Level Indication: |
|
Separately
display of the Output 1 level (heating) and the Output 2 level (cooling). |
| Output Status Indication: |
|
Two LED indicators (OUT 1 and
OUT 2) are lit when their respective output is ON. |
| Output Level Limits: |
|
|
- For 1
control output: From 0 to 100% of the output span. |
|
|
|
- For 2 control outputs: From
-100 to 100% of the main (heating) output span. |
|
|
|
This
function can be made active at instrument startup for a configurable time, and
it can be left active in order to avoid thermal shock or preheating. |
| Relay
Outputs Output Cycle Time: |
|
Configurable from 1 second to
99 seconds. |
| Output 1: |
|
|
SPDT
contact. The selection of the NO or NC contact is made by jumper. |
| Contact
Rating: |
|
|
3 Amps at 250 Vac on a
resistive load. |
| Output 2 (Cooling): |
|
|
SPST contact
with rated current 2 Amps at 250 Vac on a resistive load. |
| Logic
Voltage for SSR Driver (Output 1 Only): |
|
|
|
Logic Level 0: |
|
Less than
0.5 Vdc. |
|
Logic Level 1: |
|
14 Vdc ±20% @ 17 mA
max. |
|
|
|
24 Vdc
±20% @ 1 mA max. |
| Output Safety
Value: |
|
|
When the instrument detects an
out of range or a sensor break condition, it can force the output to a
configurable safety value. |
Output Disable Function |
| This
function disables the control output allowing the instrument to operate as an
indicator. When control is resumed, turn off is disabled and the
instrument will operate as follows: the integral component of the output signal
will be set to zero, the soft start function will be enabled, and the alarm
masking function will be enabled. |
Alarms |
| This
instrument is equipped with two independent outputs configurable as: |
|
|
|
- Heating +
Alarm 1 + Alarm 2 |
|
|
|
- Heating + Cooling + Alarm
1 |
| An optional 4 output is available as Alarm 3 or the heater
breakdown alarm output. |
| Output
Action: |
|
|
Direct or reverse function
configurable. |
| Alarm Functions: |
|
|
Each alarm
can be configured as process alarm, band alarm or deviation alarm. |
| Alarm Reset: |
|
|
Automatic or manual reset
programmable on each alarm. |
| Alarm Masking: |
|
|
Each alarm
can be configured as a masked or standard alarm. Alarm masking allows
suppression of alarm indicators at startup and after a setpoint change. |
| Alarm
Indications: |
|
|
Two indicators show when the
respective alarm is ON. |
| Alarm Outputs: |
|
|
Two SPST
relays. Contact rated at 2 Amps, 250 Vac on resistive load. |
| Process Alarm Operating Mode: |
|
High or low configurable. |
| Alarm Setpoint: |
|
|
Configurable
in engineering units within the entire range. |
| Hysteresis: |
|
|
Configurable from 0.1% to
10.0% of the input span. |
| Band Alarm Operating Mode: |
|
Inside or
outside band configurable. |
| Alarm
Setpoint: |
|
|
Configurable from 0 to 500
units. |
| Hysteresis: |
|
|
Configurable
from 0.1% to 10.0% of the input span. |
| Deviation Alarm Operating Mode: |
|
High or low configurable. |
| Alarm Setpoint: |
|
|
Configurable
from -500 to 500 units. |
| Hysteresis: |
|
|
Configurable from 0.1% to
10.0% of the input span. |
| Hbd Alarm |
|
|
(for
instruments with heater breakdown input option. |
| Operating
Mode: |
|
|
Low alarm. |
| Alarm Setpoint: |
|
|
Configurable
in engineering units within the readout span. |
Digital
Communications (Optional) |
| Type: |
|
|
RS-485. |
| Protocol
Type: |
|
|
MODBUS, JBUS, or Barber-Colman
proprietary polling/selecting. |
| Baud Rate: |
|
|
Keyboard
configurable from 600 to 19200 BAUD. |
| Byte Format: |
|
|
7 or 8 bit configurable. |
| Parity: |
|
|
Even, odd or
none configurable. |
| Stop Bit: |
|
|
One. |
| Address: |
|
|
- From 1 to
31 for Barber-Colman protocol. |
|
|
|
- From 1 to 255 for all other
protocols. |
| Output Voltage Levels: |
|
According to
EIA standards. |
|
|
|
|