TECHNICAL SPECIFICATION (7EF/7HF)
Case: ABS black. Self-extinguishing degree V-0 according to UL,VDE and CSA.
Front Protection: Designed and tested for IP65 and NEMA 4X for indoor locations (when panel gasket is installed).
Installation: Panel mounting by means of brackets.
Rear Terminal Block: Up to 21 screw terminals, with safety rear cover.
Dimensions: 48 x 96 mm (1.890 x 3.780 in.) according to DIN 43700; 116 mm (4.567 in.) deep.
Weight: 400 grams maximum (1 pound).
Power Supply (Switch Mode): 100 to 240 Vac, 50/60 Hz (10% to -15% of the nominal value).
Power Consumption: 11 VA.
Insulation Resistance: Greater than 100 MW according to IEC 348.
Isolation Voltage: 1500 Vrms according to IEC 348.
D/A Conversion: Dual slope integration.
Noise Immunity: a) Electrical fast transient/burst requirements: Severity Level 3 (according to IEC 801-4).
b) Electric discharge requirements: Severity Level 8 (according to IEC 801-2).
Sampling Time: 250 ms for linear inputs.
500 ms for TC or RTD inputs.
Accuracy: ±0.2% full scale value @ 25°C and nominal power supply voltage.
Common Mode Rejection Ratio: 120 dB @ 50/60 Hz.
Normal Mode Rejection Ratio: 60 dB @ 50/60 Hz.
Operating Temperature: From 0 to 50°C.
Storage Temperature: From -20 to 70°C.
Humidity: From 20% to 85% RH non-condensing.
Protection: a) Watch dog for automatic reset.
b) DIP Switches for configuration and calibration parameters.

Inputs (All inputs are factory calibrated and selectable from the keyboard.)
Thermocouple Types: J, K, L, R, S and N are keyboard configurable.
Engineering Units: °C and °F keyboard configurable.
Sensor Break: Downscale or upscale programmable. On RTD inputs, an OVERRANGE is indicated when input resistance is less than 15 W (short circuit sensor detection.)
Reference Junction: Automatic compensation for an ambient temperature between 0 and 50 °C.
Reference Junction Drift: 0.1 °C/°C.
Input Impedance: Greater than 1 MW.
Calibration: According to IEC 584-1.

RTD Input
RTD Type: Pt 100 3 wire connection.
Calibration: According to DIN 43760.
Line Resistance: Maximum of 20 W/wire with no appreciable error.
Engineering Units: °C and °F keyboard configurable.
Sensor Break Detection: Open sensor (one or more open wires), and short circuit sensor detection.

mAdc and Vdc Linear Inputs
mAdc Input (Standard): 0 to 20 mAdc and 4 to 20 mAdc keyboard configurable.
Input Impedance: Less than 5 W.
Vdc Input: 0 to 5 Vdc and 1 to 5 Vdc, configurable. Input impedance greater than 200 KW.
0 to 10 Vdc and 2 to 10 Vdc configurable. Input impedance greater than 400 KW.
0 to 60 mVdc and 12 to 60 mV configurable. Input impedance greater than 1 MW.
Readout: Keyboard configurable from -1999 to 4000.
Decimal Point: Configurable to any position.

Current Transformer Input for OUT 1 Heater Breakdown Detection
(Optional, 7EF/7HF only) This feature allows measurement of the load current by means of a current transformer and signals an alarm condition when the current is below a pre-programmed threshold value.
Input Range: 50 mAac.
Scaling: Configurable from 10 Amps to 100 Amps (with a 1 Amp step).
Resolution: - for full scale up to 20 Amps: 0.1 Amp.
- for full scale from 21 Amps to 100 Amps: 1 Amp.
Active Period: - for relay output: NO or NC configurable.
- for SSR output: logic level 1 or 0 configurable.
Minimum On Time to Perform the measurement: 50 ms.

Logic Input
The 7EF/7HF is equipped with a logic input to select between the main and auxiliary setpoint (SP or SP2).

Setpoints
Two setpoints available: - Main Setpoint (SP).
- Auxiliary Setpoint (SP2).
Setpoint Transfer: Transfer between SP and SP2 by logic input (contact closure). Transfer can be either by a step or by a ramp with two different configurable rates of change (ramp up and ramp down).
Setpoint Limits: Setpoint low limit and setpoint high limit are configurable.

Control Action
Algorithm: PID - Smart AT.
Type: One (heating) or two (heating/cooling) control outputs.
Proportional Band: Configurable - From 1.0% to 100.0% of the input span for a process with one control output.
- From 1.5% to 100.0% of the input span for a process with two control outputs.
Setting the PB equal to 0 changes the control action to ON/OFF.
Hysteresis (for ON/OFF control action): Configurable from 0.1% to 10.0% of the input span.
Integral Time: Configurable from 20 seconds to 20 minutes (or off).
Derivative Time: Configurable from 1 second to 10 minutes (or off).
Integral Preload: Configurable: - for 1 control output, from 0 to 100% of the output range.
- for 2 control outputs, from -100% to 100% of the heating/cooling output range.
Out 1 (heating) Cycle Time: From 1 to 200 seconds.
AUTO/MANUAL Mode: Selectable by front pushbutton.
AUTO/MANUAL Transfer: Bumpless.
Two Control Outputs (Heating/Cooling)
Relative Cooling Gain: Keyboard configurable from 0.20 to 1.00.
Cooling Cycle Time: From 1 to 200 seconds.
Overlap/Deadband: Keyboard configurable from -20% (deadband) to 50% (overlap) of the PB.
NOTE: By setting the proper cooling medium (air, oil or water) during configuration, the instrument will automatically set the cooling (OUT 2) parameters.

Control Outputs
Type: Time Proportioning.
Direct/Reverse Action: Keyboard configurable.
Output Level Indication: Separately display of the Output 1 level (heating) and the Output 2 level (cooling).
Output Status Indication: Two LED indicators (OUT 1 and OUT 2) are lit when their respective output is ON.
Output Level Limits: - For 1 control output: From 0 to 100% of the output span.
- For 2 control outputs: From -100 to 100% of the main (heating) output span.
This function can be made active at instrument startup for a configurable time, and it can be left active in order to avoid thermal shock or preheating.
Relay Outputs Output Cycle Time: Configurable from 1 second to 99 seconds.
Output 1: SPDT contact. The selection of the NO or NC contact is made by jumper.
Contact Rating: 3 Amps at 250 Vac on a resistive load.
Output 2 (Cooling): SPST contact with rated current 2 Amps at 250 Vac on a resistive load.
Logic Voltage for SSR Driver (Output 1 Only):
Logic Level 0: Less than 0.5 Vdc.
Logic Level 1: 14 Vdc ±20% @ 17 mA max.
24 Vdc ±20% @ 1 mA max.
Output Safety Value: When the instrument detects an out of range or a sensor break condition, it can force the output to a configurable safety value.

Output Disable Function
This function disables the control output allowing the instrument to operate as an indicator. When control is resumed, “turn off” is disabled and the instrument will operate as follows: the integral component of the output signal will be set to zero, the soft start function will be enabled, and the alarm masking function will be enabled.

Alarms
This instrument is equipped with two independent outputs configurable as:
- Heating + Alarm 1 + Alarm 2
- Heating + Cooling + Alarm 1
An optional 4 output is available as Alarm 3 or the heater breakdown alarm output.
Output Action: Direct or reverse function configurable.
Alarm Functions: Each alarm can be configured as process alarm, band alarm or deviation alarm.
Alarm Reset: Automatic or manual reset programmable on each alarm.
Alarm Masking: Each alarm can be configured as a masked or standard alarm. Alarm masking allows suppression of alarm indicators at startup and after a setpoint change.
Alarm Indications: Two indicators show when the respective alarm is ON.
Alarm Outputs: Two SPST relays. Contact rated at 2 Amps, 250 Vac on resistive load.
Process Alarm Operating Mode: High or low configurable.
Alarm Setpoint: Configurable in engineering units within the entire range.
Hysteresis: Configurable from 0.1% to 10.0% of the input span.
Band Alarm Operating Mode: Inside or outside band configurable.
Alarm Setpoint: Configurable from 0 to 500 units.
Hysteresis: Configurable from 0.1% to 10.0% of the input span.
Deviation Alarm Operating Mode: High or low configurable.
Alarm Setpoint: Configurable from -500 to 500 units.
Hysteresis: Configurable from 0.1% to 10.0% of the input span.
Hbd Alarm (for instruments with heater breakdown input option.
Operating Mode: Low alarm.
Alarm Setpoint: Configurable in engineering units within the readout span.

Digital Communications (Optional)
Type: RS-485.
Protocol Type: MODBUS, JBUS, or Barber-Colman proprietary polling/selecting.
Baud Rate: Keyboard configurable from 600 to 19200 BAUD.
Byte Format: 7 or 8 bit configurable.
Parity: Even, odd or none configurable.
Stop Bit: One.
Address: - From 1 to 31 for Barber-Colman protocol.
- From 1 to 255 for all other protocols.
Output Voltage Levels: According to EIA standards.