Universal Input (7 T/C, RTD, mV, V, mA)
PID and Smart AT Autotuning
NEMA 4X, IP65
Algorithms for Heat or Heat/Cool Control
Up to 4 Outputs, 3 Independent Alarms
Control Output Disable Function
Remote Selection of up to 4 Setpoints
Digital Communications |
 |
|
Designed for equipment manufacturers requiring
analog process control functions and a full suite of advanced features, the 7SC
offers outstanding performance as a 4-digit 1/8 DIN controller. The 7SC is
configurable for heat or heat/cool PID control with Smart AT auto or adaptive
tuning, universal inputs, up to 4 outputs (including one analog output) and up
to 3 independent alarms. It is ideal for demanding applications in plastics,
rubber fibers, annealing, small ovens, and other processes requiring 4 digit
accuracy. The 7SC has a bright dual display for process temperature and
setpoint, and 10 LED beacons for operating status. The analog and two relay
outputs can be programmed as heating +2 alarms or heating/cooling + alarm.
|
|
Alternately, OP2 can
be an SSR logic output. The isolated analog output can alternatively be
programmed as a retransmission of the PV or operating SP. OP4 can be configured
as Alarm 3. Alarms can be process, deviation or band type, direct or reverse,
with masking and programmable automatic or manual reset. An alarm standby
feature allows masking of alarm conditions until the PV reaches the low alarm
threshold. A non-isolated 24 Vdc transducer power supply is a standard feature.
Optional RS-485 communications are available for connection to supervisory
computers. A NEMA 4X front panel allow the 7SC to work in washdown or dusty
environments. |
| A Variety of
Standard and Optional Features |
Logic Common
|
 |
| Among the
7EC's standard features are bumpless auto/manual transfer, password security
and Auto Comp® sensor break. The 7EC also has an "output off" function
which disables the control output, allowing the instrument to operate as an
indicator but return smoothly to control when the output is again enabled. The
7EC is equipped with 2 logic inputs used to select between up to 4 setpoints.
Transfer can be step or ramp, with different configurable rates for ramp up and
ramp down. |
Logic
Input Logic Input 2 |
|
SP1 - SP4 Select
CT Part Number: 7ER-Rx000-0000 x=1 (10A),
x=2 (25A), x=4 (50A), x=5 (100A) |
|