TECHNICAL SPECIFICATION (2604) |
| Control options |
|
|
|
| No. of loops |
|
|
1, 2 or 3 loops |
| Options |
|
Cascade, Ratio or
Override |
| Modes |
|
|
PID, ON/OFF
or Valve Position |
| Applications |
|
Carbon Potential,
Humidity |
| STANDARD I/O |
Precision PV Input |
|
|
| Accuracy |
|
|
±0.1% |
| Ranges |
|
|
mV, mA,
volts or RTD (PT100) |
| Thermocouple
types |
|
|
J,K,L,N,R,S,B,PII,C, plus
others |
| Cold junction |
|
|
Ext 0°C,
45°C or 50°C |
| Analogue input |
|
|
|
| Allocation |
|
|
1
fitted |
| Accuracy |
|
|
±0.1% |
| Ranges |
|
|
-10V to 10V
or 0 to 20mA |
| Digital I/O |
|
|
|
| Types |
|
|
1 digital
input |
|
|
|
7 Bi-directional
input/outputs |
|
|
|
1 Changeover
relay |
| MODULES |
Digital
outputs |
|
|
| Types |
|
|
Single
relay, dual relay, Single Triac, Dual Triac, Single Logic and Triple Logic
module |
| Allocation |
|
|
Slot 1, 3, 4, 5 or 6 (Max 3
Triacs per unit) |
| Digital inputs |
|
|
|
| Types |
|
|
Triple contact input, Triple
logic input |
| Allocation |
|
|
Slot 1, 3,
4, 5 or 6 |
| Analogue
outputs |
|
|
| Types |
|
|
DC Control
or DC Retransmission (5 Max) |
| Allocation |
|
|
Slot 1, 3, 4, 5 or 6 |
| Range |
|
|
0 to 20mA or
0 to 10Vdc |
| Dual
Analogue outputs |
|
|
| Allocation |
|
|
Slot 1, 4 or
5 |
| Range |
|
|
4-20mA or 24Vdc transmitter
PSU |
| High Resolution Analogue output |
|
|
| Allocation |
|
|
Slot 1, 4 or 5 |
| Range |
|
|
4-20mA and
24Vdc transmitter PSU |
| Transmitter PSU |
|
|
|
| Allocation |
|
|
Slot 1, 3,
4, 5 or 6 |
| Transmitter |
|
|
24Vdc @ 20mA |
| Transducer supply |
|
|
| Bridge
voltage |
|
|
Software selectable, 5 or
10Vdc |
| Bridge resistance |
|
|
300W to 15Kohms |
| Potentiometer input |
|
|
| Potentiometer resistance |
|
330W to 150Kohms |
| Precision
PV input (Module) |
|
|
| Allocation |
|
|
Slot 3 or
6 |
| Accuracy |
|
|
±0.1% |
| Ranges |
|
|
mV, mA,
volts or RTD (PT100) |
| Thermocouple
types |
|
|
J, K, T, L, N, R, S, B, PII,
C, plus others |
| Cold junction |
|
|
Ext 0°C,
45°C or 50°C |
| Dual
(Probe) input |
|
|
| Allocation |
|
|
Slot 3 or
6 |
| Accuracy |
|
|
±0.1% |
| Ranges |
|
|
mV, mA,
volts or RTD (PT100) |
| Thermocouple
types |
|
|
J, K, T, L, N, R, S, B, PII,
C, plus others |
| Cold junction |
|
|
Ext 0°C,
45°C or 50°C |
| Analogue
input (module) |
|
|
| Allocation |
|
|
Slot 1, 3, 4
or 6 |
| Accuracy |
|
|
±0.2% |
| Ranges |
|
|
mV, mA,
volts or RTD (PT100) |
| Thermocouple
types |
|
|
J, K, T, L, N, R, S, B, PII,
C, plus others |
| Cold junction |
|
|
Ext 0°C,
45°C, or 50°C |
| SETPOINT
PROGRAMMER |
|
|
| No profiles |
|
|
1, 2 or 3
profiles |
| No. of
programs |
|
|
50 programs max. |
| No. of segments |
|
|
500 time to
target segments (Max) or 400 ramp rate segments (max.) |
| Event
outputs |
|
|
Up to 16 |
| I/O
Expander |
|
|
|
| 10 I/O
Version |
|
|
4 Changeover and 6 normally
open relay contacts |
|
|
|
10 Logic
inputs |
| 20 I/O
Version |
|
|
4 Changeover and 16 normally
open contacts |
|
|
|
20 Logic
inputs |
| ADVANCED
FUNCTIONS |
|
|
| Application blocks |
|
|
32 digital
operations |
|
|
|
24 analogue operations |
|
|
|
12 user
values |
| Timers |
|
|
4 ON pulse, OFF delay, one
shot and min-ON |
| Totalisers |
|
|
4, trigger
level and reset input |
| Pattern
generators |
|
|
16 patterns each with 16
bits |
| Real time clock |
|
|
Day of week
and time |
| Customisable screens |
|
8 user screens |
| User switches |
|
|
8, toggle
and momentary function |
| Slave
communications |
|
|
| Allocation |
|
|
Slot H or J
(DeviceNet/Profibus slot H only) |
| Types |
|
|
Profibus DP RS485 |
|
|
|
Modbus RTU
RS485 (2 wire), RS485 (4 wire) or RS232 |
|
|
|
DeviceNet |
|
|
|
EI-Bisyc
(subset of parameters) |
| Master
communications |
|
|
| Allocation |
|
|
Slot J |
| Types |
|
|
Modbus RTU RS485 (2 wire),
RS485 (4 wire) or RS232 |
| Parameters |
|
|
25
read/write |
| GENERAL
SPECIFICATION |
|
|
| Display range |
|
|
5 digits up
to 3 decimal places |
|
|
|
85 to 264Vac, 20 watts (max.)
or 24Vdc or ac, 10 watts (max) |
| Operating ambient |
|
|
0 to
50°C and 5 to 95%RH non condensing |
| Storage
temperature |
|
|
-10 to 70°C |
| Panel seal |
|
|
IP65 |
| EMC
standards |
|
|
EN50081-1 and EN50082-2
generic standards - suitable for domestic, commercial and light industrial as
well as heavy industrial environments |
| Safety standards |
|
|
Meets
EN61010 installation category II, pollution degree 2 |
| Atmospheres |
|
|
Not suitable for use above
2000m or in explosive or corrosive atmospheres |
|