TECHNICAL SPECIFICATION (2604)
Control options
No. of loops 1, 2 or 3 loops
Options Cascade, Ratio or Override
Modes PID, ON/OFF or Valve Position
Applications Carbon Potential, Humidity
STANDARD I/O Precision PV Input
Accuracy ±0.1%
Ranges mV, mA, volts or RTD (PT100)
Thermocouple types J,K,L,N,R,S,B,PII,C, plus others
Cold junction Ext 0°C, 45°C or 50°C
Analogue input
Allocation 1 fitted
Accuracy ±0.1%
Ranges -10V to 10V or 0 to 20mA
Digital I/O
Types 1 digital input
7 Bi-directional input/outputs
1 Changeover relay
MODULES Digital outputs
Types Single relay, dual relay, Single Triac, Dual Triac, Single Logic and Triple Logic module
Allocation Slot 1, 3, 4, 5 or 6 (Max 3 Triacs per unit)
Digital inputs
Types Triple contact input, Triple logic input
Allocation Slot 1, 3, 4, 5 or 6
Analogue outputs
Types DC Control or DC Retransmission (5 Max)
Allocation Slot 1, 3, 4, 5 or 6
Range 0 to 20mA or 0 to 10Vdc
Dual Analogue outputs
Allocation Slot 1, 4 or 5
Range 4-20mA or 24Vdc transmitter PSU
High Resolution Analogue output
Allocation Slot 1, 4 or 5
Range 4-20mA and 24Vdc transmitter PSU
Transmitter PSU
Allocation Slot 1, 3, 4, 5 or 6
Transmitter 24Vdc @ 20mA
Transducer supply
Bridge voltage Software selectable, 5 or 10Vdc
Bridge resistance 300W to 15Kohms
Potentiometer input
Potentiometer resistance 330W to 150Kohms
Precision PV input (Module)
Allocation Slot 3 or 6
Accuracy ±0.1%
Ranges mV, mA, volts or RTD (PT100)
Thermocouple types J, K, T, L, N, R, S, B, PII, C, plus others
Cold junction Ext 0°C, 45°C or 50°C
Dual (Probe) input
Allocation Slot 3 or 6
Accuracy ±0.1%
Ranges mV, mA, volts or RTD (PT100)
Thermocouple types J, K, T, L, N, R, S, B, PII, C, plus others
Cold junction Ext 0°C, 45°C or 50°C
Analogue input (module)
Allocation Slot 1, 3, 4 or 6
Accuracy ±0.2%
Ranges mV, mA, volts or RTD (PT100)
Thermocouple types J, K, T, L, N, R, S, B, PII, C, plus others
Cold junction Ext 0°C, 45°C, or 50°C
SETPOINT PROGRAMMER
No profiles 1, 2 or 3 profiles
No. of programs 50 programs max.
No. of segments 500 time to target segments (Max) or 400 ramp rate segments (max.)
Event outputs Up to 16
I/O Expander
10 I/O Version 4 Changeover and 6 normally open relay contacts
10 Logic inputs
20 I/O Version 4 Changeover and 16 normally open contacts
20 Logic inputs
ADVANCED FUNCTIONS
Application blocks 32 digital operations
24 analogue operations
12 user values
Timers 4 ON pulse, OFF delay, one shot and min-ON
Totalisers 4, trigger level and reset input
Pattern generators 16 patterns each with 16 bits
Real time clock Day of week and time
Customisable screens 8 user screens
User switches 8, toggle and momentary function
Slave communications
Allocation Slot H or J (DeviceNet/Profibus slot H only)
Types Profibus DP RS485
Modbus RTU RS485 (2 wire), RS485 (4 wire) or RS232
DeviceNet
EI-Bisyc (subset of parameters)
Master communications
Allocation Slot J
Types Modbus RTU RS485 (2 wire), RS485 (4 wire) or RS232
Parameters 25 read/write
GENERAL SPECIFICATION
Display range 5 digits up to 3 decimal places
85 to 264Vac, 20 watts (max.) or 24Vdc or ac, 10 watts (max)
Operating ambient 0 to 50°C and 5 to 95%RH non condensing
Storage temperature -10 to 70°C
Panel seal IP65
EMC standards EN50081-1 and EN50082-2 generic standards - suitable for domestic, commercial and light industrial as well as heavy industrial environments
Safety standards Meets EN61010 installation category II, pollution degree 2
Atmospheres Not suitable for use above 2000m or in explosive or corrosive atmospheres