TECHNICAL SPECIFICATION (2408(f), 2404(f)) |
| Process value
inputs |
|
|
| Low level range |
|
|
-100 to + 100mV |
| High level
range |
|
0-20mA or
0-10Vdc |
| Sample
rate |
|
|
9Hz |
| Resolution |
|
<2µV for low level
inputs |
|
|
|
<0.2mV
for high level inputs |
| Linearity |
|
|
Better than 0.2°C
±1LSD |
| Calibration accuracy |
|
|
±1°C or ±0.2% of reading, whichever is
greater |
| User
calibration |
|
|
Low and high offsets can be
applied |
| Input filtering |
|
|
OFF to 999.9
seconds |
| Thermocouple
types |
|
|
Refer to the ordering code
sensor input table |
| Cold Junction compensation |
|
In automatic
mode, >30 to 1 rejection of ambient temperature change OR external 0°C,
45°C, 50°C references |
| 3-wire Pt100
input |
|
|
Bulb current: 0.3mA. Up to
22ohm in each lead without error |
| Potentiometer input |
|
|
330 to
15Kohm |
| Analogue input functions |
|
Process value, remote
setpoint, setpoint trim, external power limit, feedforward input, Valve
position feedback |
| Second process value input functions |
|
Select min,
select max, derived value, transfer to 2nd PV |
Digital
inputs (Isolated except for fixed digital
inputs 1 & 2) |
| Contact closure |
Open circuit voltage: |
|
24 to
30Vdc |
| inputs |
Short circuit
current: |
|
24 to 29mA |
|
Off state: |
|
<100ohms
input resistance |
|
On state: |
|
>28Kohm input
resistance |
| Logic inputs |
Off state: |
|
-3 to 5Vdc @
<-0.4mA |
| (Current
sinking) |
On
state: |
|
10.8 to 30Vdc @
2.5mA |
Digital outputs |
| Relay rating |
|
|
2A, 264Vac resistive |
| Single logic output* |
|
|
18Vdc, 20mA
(non-isolated) |
| Triple logic
output |
|
|
12Vac, 8mA per channel
(isolated) |
| Triac |
|
|
1A, 264Vac
resistive (isolated) |
| High current
output |
Rating: |
|
10amp, 264Vac resistive (2404
f only) (isolated) |
Analogue outputs |
| Range |
|
|
0-20mA, 0-10VDC
(isolated) |
| Resolution |
|
|
1 part in
10,000 for analogue retrans. |
|
|
|
1 part in 7,000 for DC control
outputs |
| Transmitter supply |
|
|
20mA,
24Vdc |
Control
functions |
| Control modes |
|
|
On/Off, PID
or motorised valve control, with or without a feedback potentiometer |
| Cooling
algorithms |
|
|
Linear, water, fan, oil |
| Tuning |
|
|
One-shot and
continuous adaptive tuning |
| Number of PID
sets |
|
|
Two |
| Auto manual control |
|
|
Bumpless
transfer or forced manual output available |
| Setpoint rate
limit |
|
|
Display units per sec, per min
or per hour |
Alarms |
| Number of
alarms |
|
|
Four |
| Alarm types |
|
|
High, low,
deviation high, deviation low, deviation band, rate of change. |
| Alarm modes |
|
|
Latching or non-latching.
Blocking. |
|
|
|
Energised or
de-energised in alarm |
Setpoint
programming |
| Number of
programs |
|
|
Up to four |
| Segments per prog |
|
|
16 |
| Event
outputs |
|
|
Up to eight |
Communications (All modules
are isolated) |
| Profibus |
|
|
High speed, RS485. Up to
1.5Mb/s |
| Modbus ® |
|
|
RS232,
2-wire RS485 and 4-wire |
|
|
|
RS485 modules |
PDSIO |
| Slave input
(isolated) |
|
|
Remote setpoint with holdback
to master |
| Master output* |
|
|
Retransmission of setpoint, process value or output |
General |
| Display range |
|
|
Four digits
with up to two decimal places |
| Supply |
|
|
100 to 240Vac -15%, +10% 48 to
62Hz, OR 24Vdc or ac -15%, +20%. 10W max. |
| Operating ambient |
|
|
0 to
55°C and 5 to 95% RH non-condensing |
| Storage
temperature |
|
|
-10 to +70°C |
| Panel sealing |
|
|
IP54 |
| Dimensions
(mm) |
2408f: |
|
48W x 96H x 150D |
|
2404f: |
|
96W x 96H x
150D |
| EMC
standards |
|
|
EN50081-2 & EN50082-2
generic standards for industrial environments |
| Safety standards |
|
|
Meets
EN61010, installation category II, pollution degree 2 |
| Atmospheres |
|
|
Not suitable for use above
2000m or in explosive or corrosive atmospheres. |
| * These inputs or outputs are not isolated from the main
process value input. |