- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  

TECHNICAL SPECIFICATION (2408(f), 2404(f))
Process value inputs
Low level range -100 to + 100mV
High level range 0-20mA or 0-10Vdc
Sample rate 9Hz
Resolution <2µV for low level inputs
<0.2mV for high level inputs
Linearity Better than 0.2°C ±1LSD
Calibration accuracy ±1°C or ±0.2% of reading, whichever is greater
User calibration Low and high offsets can be applied
Input filtering OFF to 999.9 seconds
Thermocouple types Refer to the ordering code sensor input table
Cold Junction compensation In automatic mode, >30 to 1 rejection of ambient temperature change OR external 0°C, 45°C, 50°C references
3-wire Pt100 input Bulb current: 0.3mA. Up to 22ohm in each lead without error
Potentiometer input 330 to 15Kohm
Analogue input functions Process value, remote setpoint, setpoint trim, external power limit, feedforward input, Valve position feedback
Second process value input functions Select min, select max, derived value, transfer to 2nd PV

Digital inputs (Isolated except for fixed digital inputs 1 & 2)
Contact closure Open circuit voltage: 24 to 30Vdc
 inputs Short circuit current: 24 to 29mA
Off state: <100ohms input resistance
On state: >28Kohm input resistance
Logic inputs Off state: -3 to 5Vdc @ <-0.4mA
 (Current sinking) On state: 10.8 to 30Vdc @ 2.5mA

Digital outputs
Relay rating 2A, 264Vac resistive
Single logic output* 18Vdc, 20mA (non-isolated)
Triple logic output 12Vac, 8mA per channel (isolated)
Triac 1A, 264Vac resistive (isolated)
High current output Rating: 10amp, 264Vac resistive (2404 f only) (isolated)

Analogue outputs
Range 0-20mA, 0-10VDC (isolated)
Resolution 1 part in 10,000 for analogue retrans.
1 part in 7,000 for DC control outputs
Transmitter supply 20mA, 24Vdc

Control functions
Control modes On/Off, PID or motorised valve control, with or without a feedback potentiometer
Cooling algorithms Linear, water, fan, oil
Tuning One-shot and continuous adaptive tuning
Number of PID sets Two
Auto manual control Bumpless transfer or forced manual output available
Setpoint rate limit Display units per sec, per min or per hour

Alarms
Number of alarms Four
Alarm types High, low, deviation high, deviation low, deviation band, rate of change.
Alarm modes Latching or non-latching. Blocking.
Energised or de-energised in alarm

Setpoint programming
Number of programs Up to four
Segments per prog 16
Event outputs Up to eight

Communications (All modules are isolated)
Profibus High speed, RS485. Up to 1.5Mb/s
Modbus ® RS232, 2-wire RS485 and 4-wire
RS485 modules

PDSIO
Slave input (isolated) Remote setpoint with holdback to master
Master output* Retransmission of setpoint, process value or output

General
Display range Four digits with up to two decimal places
Supply 100 to 240Vac -15%, +10% 48 to 62Hz, OR 24Vdc or ac -15%, +20%. 10W max.
Operating ambient 0 to 55°C and 5 to 95% RH non-condensing
Storage temperature -10 to +70°C
Panel sealing IP54
Dimensions (mm) 2408f: 48W x 96H x 150D
2404f: 96W x 96H x 150D
EMC standards EN50081-2 & EN50082-2 generic standards for industrial environments
Safety standards Meets EN61010, installation category II, pollution degree 2
Atmospheres Not suitable for use above 2000m or in explosive or corrosive atmospheres.
* These inputs or outputs are not isolated from the main process value input.
Last updated January 8, 2004