| SPECIFICATIONS
for T755X |
|
Physical (version dependent) |
| |
T7550 |
T7551 |
T7555 |
T7556 |
Notes |
|
Mounting: |
Floor |
Floor |
Wall |
Wall |
|
| External dimensions
(mm): |
800Wx500Dx2000H |
1200Wx400Dx2000H |
800Wx 400Dx1200H |
600Wx400Dx600H |
|
|
Plinth -none/100/200 (mm): |
Yes/Yes/Yes |
Yes/Yes/Yes |
Yes/No/No |
Yes/No/No |
|
| Cable entry -
Top/Bottom |
Yes/Yes |
Yes/Yes |
Yes/Yes |
Yes/Yes |
|
|
Door hinge - Left/Right |
Yes/Yes |
Both |
Yes/Yes |
Yes/Yes |
|
| Light: |
Yes |
Yes |
Yes |
(for bottom
entry only) |
|
|
Thermostat: |
Yes |
Yes |
Yes |
Yes |
Always fitted |
| N+1
(redundant) PSU: |
Yes |
Yes |
Yes |
Yes |
|
| Inlet
fan/filter: |
Yes |
Yes |
Yes |
Yes |
|
| Internal equipment |
|
|
|
|
|
|
T940 and battery: |
2/Yes |
2/Yes |
2/Yes |
-/No |
|
| T303: |
1 |
1 |
- |
- |
Choice between
T921 and T932 |
| CPUs |
|
|
|
|
|
| T800: |
1 |
1 |
1 |
1 |
|
| T630: |
6 |
6 |
4 |
3 |
|
| 2500 16 way: |
6 |
8 |
4 |
2 |
|
| 2500 8 way: |
8 |
8 |
4 |
4 |
Alternative to 16
way |
| IS barrier option: |
|
|
|
|
|
| ‘External’ alarms
pre-wired: |
Yes |
Yes |
Yes |
Yes |
Consult factory DI8 in
1st base,
1st position |
| Capacity I/O points: |
384 |
512 |
256 |
128 |
|
| Protection category: |
IP55 |
IP55 |
IP55 |
IP55 |
Derated to IP43
when fan is fitted. |
|
|
|
Power supply |
|
|
| Supply option: |
115V ac |
230V ac |
| Input voltage
range: |
92-132V RMS |
184-264V RMS |
| Input frequency: |
47.5-63Hz |
47.5-63Hz |
| RAM backup
battery: |
4.7V
5Ah 10 days minimum holdup fully charged |
| Health status: |
Green LED plus relay (SPCO)
monitoring each PSU |
|
|
|
Accessories |
|
|
|
| S9576-TB5 ALIN
active hub: |
|
Compact hub with 3x dual RJ45 twisted pair
ports |
|
S9576-FO-ST/TB5 ALIN fiber-optic hub: |
|
Compact hub with 1x dual
RJ45 twisted pair port and 2 x fiber-optic ports |
| S9576/AI-FR/TB5
ALIN redundant ring compact hub: |
|
Compact hub with 1x dual RJ45 twisted pair
port and 2 x fiber-optic ports |
|
RS485 Profibus repeater: |
|
12Mbaud Profibus repeater
(electrical) |
| OZD Profibus
repeater: |
|
12Mbaud Profibus repeater (fiber-optic) |
|
KD485-STD (or ADE or PROG): |
|
RS232/422/485
communications isolator/converter (electrical) |
| KD485-KDF: |
|
|
Compact line driver with RS232/422/485 to
fiber-optic isolation/conversion |
| Thermostat: |
|
|
Internal temperature alarm
contact (set at 50(C) |
|
|
General/environmental |
|
|
| Storage
temperature: |
|
–25°C to +85°C |
|
Operating temperature: |
|
0-35°C (0-50°C inside
enclosure) |
| Relative humidity: |
|
|
5 to 95% (non-condensing) |
| Design
standards |
|
| |
Protection: |
|
BS EN60529 |
| |
EMC emission: |
|
EN50081-1 |
| |
EMC immunity: |
|
EN50082-2 |
| |
Electrical, mechanical: |
IEC1131-2 |
| |
Safety: |
|
EN60204-1 |
| CE |
|
|
Conforms to EMC Directive
89/336/EEC and Low Voltage Directive 72/23/EEC |
|
|
Construction standards |
|
|
Enclosures are
built to EPA guidelines for construction and EMC
precautions. These are detailed in the following documents:-
T755X Enclosure construction standards HL261721 |