| SPECIFICATIONS
for T754X |
|
Physical |
|
|
|
| |
T7540 |
T7541 |
T7542 |
T7545 |
Notes |
|
Mounting: |
Floor |
Floor |
Floor |
Wall |
|
| External dimensions
(mm): |
800W × 2100H × 600D |
1200W × 2100H × 600D |
800W × 2100H × 800D |
800W × 1200H × 400D |
|
| Door |
Single |
Double |
Single |
Single |
|
| Internal equipment: |
|
|
|
|
|
|
T103: |
2/31 |
4 |
4 |
1/21 |
1.
Additional T103 subject to specified I/O capacity |
| T303: |
2 |
2 |
2 |
1 |
|
|
T1500: |
1 |
1 |
1 |
1 |
|
| T640: |
6 |
6 |
6 |
62 |
2. In lieu of second
T103 |
| IS
barrier option: |
* |
* |
* |
* |
*
consult factory |
| Capacity ALIN nodes: |
16/12* |
16/12* |
16/12* |
16/12* |
Lower figure using
passive hub |
|
Capacity, I/O points: |
256 |
512 |
512 |
128 |
|
| Power rating (maximum): |
325W |
430W |
430W |
190W |
Including T1500 |
| Protection
category: |
IP55 |
IP55 |
IP55 |
IP55 |
|
| Cable trunking (mm) |
80 × 80 |
80 × 80 |
80 × 80 |
60 × 60 |
Derated to IP43 when
ventilation fan fitted; consult factory regarding
panel mounted equipment |
|
|
| Power supply |
|
|
|
| Supply option: |
120V ac |
230V ac |
24V dc |
| Input voltage
range: |
92-132V RMS |
184-264V RMS |
18-36V |
| Input frequency: |
47.5-63Hz |
47.5-63Hz |
— |
| RAM backup
battery: |
4.7V
5Ah 10 days holdup fully charged |
| Health status: |
Green LED plus relay (SPCO)
monitoring each PSU |
|
|
|
Accessories |
|
|
|
| T221 ALIN bridge: |
|
|
Single or dual. |
|
S9572 ALIN passive hub: |
|
12-way; e.g. 9 CPU nodes
plus 2 × T221 and test point |
| S9573 ALIN adaptor: |
|
RJ45 socket for connection of ALIN test
equipment (not supplied with S9572 hub) |
| Thermostat: |
|
|
Internal temperature alarm
contact (set at 50°C) |
| Internal lamp: |
|
|
Operates via door switch when door open |
|
Fan inlet/outlet) or stirrer fan: |
|
Assists uniform
temperature distribution |
|
|
General/environmental |
| Storage
Temperature: |
|
–25°C to +85°C. |
| Operating
Temperature: |
|
0-35°C (0-50°C inside enclosure) |
| Relative humidity: |
|
|
5 to 95% (non-condensing) |
| Design standards
Protection: |
|
BS EN60529 |
| EMC emission: |
|
|
EN50081-1 |
| EMC immunity: |
|
|
EN50082-2 |
| Electrical,
mechanical: |
|
IEC1131-2 |
| Safety: |
|
|
EN60204-1 |
| Conforms to EMC
Directive 89/336/EEC
and Low Voltage Directive 72/23/EEC |
|
|
Construction standards |
| Enclosures are
built to EPA guidelines for construction and EMC
precautions. These are detailed in the following documents:– |
|
T754X Enclosure construction standards |
|
HL083637 |
| T754X Test
specification |
|
HW083636 |
| EMC
Installation |
|
|
HG08365U001 |