- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  
T754X series control enclosures

SPECIFICATIONS for T754X
Physical      
  T7540 T7541 T7542 T7545 Notes
Mounting: Floor Floor Floor Wall  
External dimensions (mm): 800W × 2100H × 600D 1200W × 2100H × 600D 800W × 2100H × 800D 800W × 1200H × 400D  
Door Single Double Single Single  
Internal equipment:          
T103: 2/31 4 4 1/21 1. Additional T103 subject to specified I/O capacity
T303: 2 2 2 1  
T1500: 1 1 1 1  
T640: 6 6 6 62 2. In lieu of second T103
IS barrier option: * * * * * consult factory
Capacity ALIN nodes: 16/12* 16/12* 16/12* 16/12* Lower figure using passive hub
Capacity, I/O points: 256 512 512 128  
Power rating (maximum): 325W 430W 430W 190W Including T1500
Protection category: IP55 IP55 IP55 IP55  
Cable trunking (mm) 80 × 80 80 × 80 80 × 80 60 × 60 Derated to IP43 when ventilation fan fitted; consult factory regarding panel mounted equipment

Power supply      
Supply option: 120V ac 230V ac 24V dc
Input voltage range: 92-132V RMS 184-264V RMS 18-36V
Input frequency: 47.5-63Hz 47.5-63Hz
RAM backup battery: 4.7V 5Ah 10 days holdup fully charged
Health status: Green LED plus relay (SPCO) monitoring each PSU

Accessories      
T221 ALIN bridge:     Single or dual.
S9572 ALIN passive hub:   12-way; e.g. 9 CPU nodes plus 2 × T221 and test point
S9573 ALIN adaptor:   RJ45 socket for connection of ALIN test equipment (not supplied with S9572 hub)
Thermostat:     Internal temperature alarm contact (set at 50°C)
Internal lamp:     Operates via door switch when door open
Fan inlet/outlet) or stirrer fan:   Assists uniform temperature distribution

General/environmental
Storage Temperature:   –25°C to +85°C.
Operating Temperature:   0-35°C (0-50°C inside enclosure)
Relative humidity:     5 to 95% (non-condensing)
Design standards Protection:   BS EN60529
EMC emission:     EN50081-1
EMC immunity:     EN50082-2
Electrical, mechanical:   IEC1131-2
Safety:     EN60204-1
Conforms to EMC Directive 89/336/EEC and Low Voltage Directive 72/23/EEC

Construction standards
Enclosures are built to EPA guidelines for construction and EMC precautions. These are detailed in the following documents:–
T754X Enclosure construction standards   HL083637
T754X Test specification   HW083636
EMC Installation     HG08365U001
Last Updated Friday, July 29, 2005