| SPECIFICATIONS
for T640 Base Unit |
|
Mechanical |
| Fascia dimensions: |
|
|
height 144mm, width 72mm. |
| Mounting panel aperture: |
|
height 138 +1 –0 mm, width 68 +0.7 –0 mm. |
| Behind
mounting panel: |
|
depth 258mm (measured from
panel front). |
| Front of mounting panel: |
|
depth 10.6mm. |
| Weight: |
|
|
2.15kg. |
|
|
Environmental |
| This product conforms to EMC
Directive 89/336/EEC amended by
93/68/EEC, and with European Low Voltage Directive
72/23/EEC. |
| Electrical safety: |
|
|
EN61010-1: 1993/A2:1995 |
| EMC emissions: |
|
|
EN50081-2 industrial |
| EMC immunity: |
|
|
EN50082-2 industrial |
| Storage temperature: |
|
–10°C to +85°C, at humidity of 5-95%
(non condensing) |
| Operating
temperature: |
|
0°C to +50°C. The
enclosure must provide
adequate ventilation, and heating if required to
avoid condensation at low temperatures. |
| Atmosphere: |
|
|
Unsuitable for use above 2000m or in
explosive or
corrosive atmospheres. |
| Front panel sealing: |
|
|
IP65. |
| Isolation: |
|
|
LIN and ALIN ports are double-insulated as
specified in EN61010 to provide protection |
| against |
|
|
electric shock. |
| Vibration: |
|
|
BS2011 Part 2.1, Test Fc, Table CII,
‘Equipment intended for large power plant and
general industrial use’ (2g, 10-55 Hz). |
| Shock: |
|
|
BS2011 Part 2.1, Test Ea, Table II, ‘General
test for
robustness, handling and transport’ (15g, 11ms). |
|
|
Relays |
| Alarm relay: |
|
|
SPST. 24V ac/dc at 1A. Absolute maximum rating 30V rms, 60V dc. |
| Watchdog
relay: |
|
|
SPST. 24V ac/dc at 1A.
Absolute maximum rating 30V rms, 60V dc. |
|
|
Power supplies |
| Mains version |
|
|
|
| Input voltage
range: |
|
90-265V ac rms. |
| Input frequency range: |
|
45-65 Hz. |
| Maximum peak
input current: |
|
1.1A. |
| Power rating: |
|
|
25VA |
| Holdup time: |
|
|
20ms. |
| Fuse: |
|
|
20 ¥ 5 mm 250V ac antisurge cartridge,
500mA. |
| Number of inputs: |
|
|
2 – Ch1 (main input) Ch 2
(backup). |
| Input voltage range: |
|
19-85 V (including rectified 48V ac). |
| Power rating: |
|
|
25VA. |
| Holdup time: |
|
|
20ms. |
| Fuse: |
|
|
20 × 5 mm 250V ac
antisurge cartridge, 2A. |
|
|
ALIN |
| The ALIN runs on screened
twisted pair. Phase A, pin 21, should be bussed to
other Phase A signals and likewise Phase B, pin 22. The
cable screen should be
connected to ALIN Gnd, pin 20. The ALIN connections are
galvanically isolated
within the T640 to assist with noise rejection and simplify
system wiring. |
| The key specifications of the
ALIN are summarized as follows: |
| Cable type: |
|
|
screened twisted pair. |
| Impedance: |
|
|
100Ω*, nominal. |
| Network topology |
|
|
single non-branching network. |
| Network terminations: |
|
100Ω* at each end. |
| Maximum load: |
|
|
16 nodes. |
| Maximum length: |
|
|
100 metres. |
| Grounding: |
|
|
single point ground per system |
| HIGH LEVEL I/O |
| The specification given below
is for a single I/O site. The T640 supports two I/O
sites. For implementation reasons the electronics for both
sites is on a single
board. The I/O connections for the second site are brought
out through a simple
interconnection board. For this reason, the high level
option cannot be chosen for
site 2 if it has not been chosen for site 1. |
|
|
Analogue inputs |
| Channels: |
|
|
4 |
| Input range: |
|
|
0-5V and 0-10V, with software selectable
range. 0-1.25V range jumper-selectable. |
| Resolution: |
|
|
0.025%. |
| Accuracy: |
|
|
0.05% of range. |
| Gain drift: |
|
|
30ppm/°C. |
| Offset drift: |
|
|
65μV/°C. |
| Input impedance: |
|
|
1 MΩ pull-down to –1.2V. |
| Break detection: |
|
|
within 1 sample. Protection strategy
selected
from within the configuration (up-scale,
down-scale, etc.). |
| Isolation: |
|
|
none. |
| Sample rate: |
|
|
9ms per configured input. Only the
configured
inputs are scanned. The fastest loop update
cannot be less than 20ms. |
|
| Internal burden
resistors |
| Values: |
|
|
HIB option — 250Ω HGB option — 62Ω. |
| Power: |
|
|
0.25W. |
| Tolerance: |
|
|
0.1%. |
| Temperature coefficient: |
|
|
15ppm/°C. |
Note.
Tolerances and temperature coefficients must be added to the
specified analogue
input tolerances. |
|
|
Transmitter power supplies |
| Channels: |
|
|
1. |
| Voltage: |
|
|
24V ±5%. |
| Current: |
|
|
0-22mA. |
| Current limit: |
|
|
30mA maximum. |
| Isolation: |
|
|
60V working. |
|
|
Voltage analogue outputs |
| Channels: |
|
|
2. |
| Output range: |
|
|
0-5V and 0-10V, with software-selectable
range.
0-1.25V range jumper-selectable |
| Resolution: |
|
|
12 bits (1.25 and 2.5mV, for the 5 and 10V
ranges resp.). |
| Accuracy: |
|
|
0.05% of range. |
| Gain drift: |
|
|
30ppm/°C. |
| Offset drift: |
|
|
70μV/°C. |
| Current drive: |
|
|
±5mA. |
| Overload detection: |
|
triggered if the output cannot maintain the
desired voltage. |
| Isolation: |
|
|
none. |
|
|
Current analogue outputs |
| Channels: |
|
|
1. |
| Output range: |
|
|
0-20mA.
(Rangeable 0-10mA, 0-20mA, 4-20mA etc.). |
| Over-range: |
|
|
22mA. |
| Resolution: |
|
|
5μA. |
| Accuracy: |
|
|
0.1%. |
| Gain drift: |
|
|
80ppm/°C. |
| Offset drift: |
|
|
0.9μA/°C. |
| Output drive: |
|
|
0-1kΩ. |
| Isolation: |
|
|
60V working. |
|
|
Digital inputs |
| Channels: |
|
|
4. |
| Thresholds: |
|
|
logic 1: 7.5V minimum
logic 0: 2.5V maximum. |
| Hysteresis: |
|
|
1.0V minimum, 3.5V maximum. |
| Input voltage: |
|
|
28V maximum. |
| Input impedance: |
|
|
200kΩ for inputs <10V, 100kΩ for inputs
>10V. |
|
|
Digital outputs |
| Channels: |
|
|
4. |
| Output
levels: |
|
|
logic 0: 0V
logic 1: 15V |
| |
|
|
(14.0V-15.5V internal supply, or external
supply). |
| External supply: |
|
|
15.5V minimum, 28V
maximum. |
| Drive impedance: |
logic 0: |
|
68Ω, 25mA maximum sink current |
| |
logic 1: |
|
2.2kΩ |
|
|
THERMOCOUPLE I/O |
| The specification given below
is for a single I/O site. The T640 supports two I/O
sites. |
|
|
mV/Thermocouple inputs |
| Channels: |
|
|
2 |
| Resolution: |
|
|
>14 bits |
| Accuracy @ 25°C: |
|
|
0.1% of mV range |
| Temperature drift: |
|
|
less than ± (0.7μV + 0.008% of reading)/°C
@ 99% confid. |
| |
|
|
(less than ± 0.3μV + 0.003% of reading)/°C
typically) |
| Input Isolation: |
|
|
250V ac rms |
| Break detection: |
|
|
within 1 sample period (with options to go
highscale,
low-scale or retain last good value). |
| 50/60Hz rejection: |
|
|
60dB SMR, 120dB CMR
(software-selectable between 50Hz and 60Hz) |
| Low level (mV)
input mode |
| Input ranges: |
|
|
–14.2 to 77mV, -7.1 to 38.5mV-3.5 to 19.2mV
and -1.8 to 9.6mV (software-selectable) |
| Thermocouple
input mode |
| Input ranges: |
J |
–210 to 1200°C |
K |
–270 to 1372°C |
| |
T |
–270 to 400°C |
S |
–50 to 1767°C |
| |
R |
–50 to 1767°C |
E |
–270 to 1000°C |
| |
B |
0 to 1820°C |
N |
0 to 1300°C |
| |
W |
1000 to 2300°C |
W3 |
0 to 2490°C |
| |
W5 |
0 to 2320°C |
MoRe |
0 to 1990°C |
|
| CJC accuracy @
25°C: |
|
–0.25°C to +1.1°C |
| CJC ambient rejection: |
|
30:1 typically |
|
|
Analogue input |
| Channels: |
|
|
1, non-isolated (software-selectable between
voltage and frequency input modes). |
| Voltage input mode |
|
|
| Input ranges: |
|
|
0 to 10V, 0 to 2.5V (software-selectable) |
| Out of range capability: |
|
± 10% |
| Accuracy @ 25°C: |
|
|
0.1% of scale |
| Resolution: |
|
|
>14 bits over 0-10V, 0-5V and 1-5V rangings |
| Temperature drift: |
|
|
less than ± (100μV + 0.008% of reading)/°C
@ 99% confid. |
| |
|
|
(less than ± 40μV + 0.004% of reading)/°C
typically) |
| Break detection: |
|
|
within 1 sample period (with options to go
high
scale, low scale or retain last good value) |
| Frequency input
mode |
|
|
| Input ranges: |
|
|
0.01Hz to 30kHz, 0.01Hz to 3kHz,
0.01Hz to 300Hz, 0.01Hz to 30Hz
(software-selectable). |
| Over-range capability |
|
up to 48kHz |
| Resolution: |
|
|
>14 bits |
| Min. pulse length |
|
|
8μs |
| Response time: |
above 20Hz: |
|
200ms maximum |
| |
below 20Hz: |
|
waveform period + 200ms |
| Maximum Accuracy: |
|
|
0.02% of reading |
| Timebase accuracy: |
|
|
0.05% over 5 years |
| Gain drift: |
|
|
<1ppm/°C |
| Max.
tantalization rate: |
|
1kHz — with simultaneous
frequency measurement
(LoFloTot set to TRUE) |
| |
|
|
48kHz — without simultaneous frequency
measurement (HiFloTot set to TRUE) |
|
|
Process output |
| Channels: |
|
|
1 |
| Output range: |
|
|
0 to 20mA can be software ranged as 0-10mA,
0-20mA, 4-20mA, etc. |
| Isolation: |
|
|
60V ac rms |
| Accuracy @ 25°C: |
|
|
0.1% of scale |
| Resolution: |
|
|
12 bits (5μA) |
| Temperature drift: |
|
less than ± (0.4μA + 0.008% of reading)/°C
@ 99% confid |
| |
|
|
(less than ± (0.2μA + 0.004% of reading)/°C
typically) |
| Output drive capability: |
|
0 to 1kΩ |
| Output fault
detection: |
|
Load fail detect (triggered if the output
cannot
maintain the desired current level), Over-driven detect
(triggered if the
output is overdriven by a larger current). |
| Output kill: |
|
|
forces the output to low-scale current
output, and
to a low-impedance state (<1V drop at 20mA).
(Kill activated by connecting Kill terminal to I+
terminal, reported in flag Status.Killed. |
|
|
Analogue output |
| Channels: |
|
|
1 |
| Output range: |
|
|
0 to 10V can be software ranged as 0-10V,
0-5V,
1-5V, etc |
| Accuracy: |
|
|
0.1% of scale |
| Resolution: |
|
|
12 bits (2.5mV) |
| Temperature drift: |
|
|
less than ± (160μV + 0.009% of reading)/°C
@ 99% confid. |
| |
|
|
(less than ± (60μV + 0.004% of reading)/°C
typically) |
| Output current drive: |
|
+5mA (source), -0.3mA (sink) |
|
| Digital
inputs |
|
|
|
| Channels: |
|
|
3 (individually isolated) |
| Input isolation: |
|
|
250V rms ac Input type: current sinking,
polarized
(but accepts ac) |
| Input voltage: |
|
|
nominally 24V |
| |
|
|
absolute max. ±40V |
| Threshold tolerance: |
|
min. input for logic ‘1’ 13.7V |
| |
|
|
max. input for logic ‘0’
5.8V |
| Input current: |
|
|
max. current for logic ‘0’ 0.1mA |
| |
|
|
min. current req. to
ensure logic ‘1’ 0.9mA |
| |
|
|
max. current at 30V 4.0mA |
|
| Digital
outputs |
|
|
|
| Channels: |
|
|
3 (non-isolated) |
| Output levels: |
|
|
software-selectable between:
24V internal or external pull-up (open-drain) |
| Internal pull-up: |
|
|
21.5V to 24.6V through 3.6kΩ |
| External pull-up: |
|
|
60V absolute maximum |
| Sink current: |
|
|
120mA maximum, <1V drop at 40mA |
| Fan-in/fan-out: |
|
|
Maximum of 2 isolated digital inputs can be
driven
from a single non-isolated digital output. |
| General |
|
|
The environment, physical, and electrical
specifications for the High-level I/O and
Thermocouple I/O assembly are the same as for the base unit.
The confidence
limits specifications quoted above have been generated in
accordance with
BS4889 —appenix A |