- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  

 Display and Controls Configuration Options Accessories
 
Configuration

Block structure
T640 supports the level of block structuring normally only found in advanced DCS systems. Each of the four control loops occupies its own task, which may be set to run at a rate appropriate to its function in the strategy. The general purpose blocks can be distributed between these tasks, T640’s internal architecture ensuring data coherence.

All but the M006 Fixed-Function versions are configured by the T500 LINtools package (see Sales specification). The Fixed- Function version is set up by simple parameterization which may be achieved either via the front panel, or using the T510 Parameterization tool software (supplied with the controller) on a PC fitted with an ALIN interface. Parameters may also be accessed online from the T500 LINview package.

Up to 250 function blocks can be configured, depending on the size of the blocks and the number of connections. The table below lists the blocks currently supported by T640 and summarises their functions.

 

The ACTION block in the MATHS category is worth particular mention. Like the other function blocks this block has pre-defined I/O. However, the action of the block can be defined using Structured Text (ST, IEC1131-3). Careful use of this block can simplify otherwise complex collections of maths and logic blocks. The ACTION configurator is part of T500 LINtools.

 
 

Continuous strategy function blocks categories

I/O Analogue and digital input/output with manual override
S6000 Communication to panel mounted control and signal processing instruments
CONDITIONING Dynamic signal processing and alarm collection
CONTROL Analogue control, simulation and communications
TIMING Timing, sequencing, totilization and events
SELECTOR Selection, switching, alarm and display page
LOGIC Boolean, latching, counting and comparison
MATHS Mathematical functions and free format expressions
CONFIG Unit identity blocks
DIAG Diagnostics
BATCH Sequencing recipe/record and discrepancy checking
 

SFC sequencing
This powerful programming technique, usually only found in large DCS and PLC environments, has been provided for applications of a sequential or state dependent nature. Typical uses include startup and shut down sequencing, the dynamic use of recipes, suppression of nuisance alarms in different operating modes, automatic takeover of controllers in fault tolerant configurations, etc.

LIN family of products
The function blocks, SFCs and peer-to-peer communications are common to the family of LIN products, allowing the appropriate level of distribution of functions for your application. T500 LINtools provides a powerful set of configuration and engineering tools for this family.

Last Updated Friday, July 29, 2005