Current Input: Factory set at 4 to 20mA. Span adjustable from 10 to23mA. Zero point adjustable from 0 to 6mA.
Voltage Input: 0 to 1Vdc, 1 to 5Vdc and 3 to15Vdc, switch selectable. Other ranges can be set in the configuration mode.
Resistance Input: Any potentiometer value from 100 Ohms to 1000 Ohms can be used for the input signal.
Input Impedance: mA Input: 250 Ohms
Vdc input: >100K Ohms
Direction of Travel: Factory set to CCW with increasing signal. Can be changed in configuration mode.
Stroke Length: Factory set for 180° rotation at full scale. Can be changed to 90° by setting a switch. Other lengths can be achieved in the configuration mode.
Control Overrides: Dry contact closure can force the actuator to either end of travel.
Deadband: Adjustable from 1% to 6% of span in 0.4% increments.
Ambient Temperature: -40° to 58°C.
Humidity: 5 to 95% rh, non-condensing.
Power Requirements: See individual model numbers. Rated to operate within 10% of nominal voltage.
Option Board: 4 to 20mA position signal and two form C relays rated at 3A, resistive. The relays can be set to activate at any point within the operating range.