- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  

SERIES 2000 GLOSSARY
Parameters Used in the Scroll Lists
NOTE: Several parameters are read only and some are for diagnostic purposes only. Most of these types of parameters have been omitted from this glossary.

Adc - Automatic Droop Compensation (PD only control)
Permits manual setting of integral (reset) value. This has the effect of moving the proportional band of resetting the measured value to equal the setpoint.
bcd - BCD input function
Permits installation of switch with user can toggle among three different setpoints or programs.
Blocking Alarm
A blocking alarm does not function until setpoint is reached. Thereafter, if an alarm condition develops, the alarm will change state.
cAL - Calibration type
NOTE: There is a factory recalibration - under cAL, select PV, then choose YES or factory.
CJC or CJC 30:1 - Cold Junction Compensation
Compensates for large variations in ambient temperature which otherwise would cause significant changes in controller input accuracy and, therefore, controller output signals. For example, in a 2404 instrument, a 30 degree change in ambient temperature will cause only a maximum error of one degree. Eurotherm's INSTANT ACCURACY™ patented technology will sense ambient changes and correct for them. Instruments without INSTANT ACCURACY will correct for CJC over 30 - 60 minutes.
CYC.C - Cool cycle time (0.2s to 999.9s)
The overall time that cooling is permitted to cycle. For example, at a 1 second cycle time, if the instrument requests a 40% output, that equals .4 second cooling on and .6 second cooling off.
CYC.H - Heat cycle time (0.2s to 999.9s)
The overall time that heating is permitted to cycle. For example, at a 1 second cycle time, if the instrument requests a 40% output, that equals .4 second heating on and .6 second heating off. Fast cycling permits the best control and the longest heater life. Select < 1 second when used with solid state relays, 10-20 seconds when used with mercury contactors, and >60 seconds when used with mechanical contactors.
dIAG - Diagnostic alarm 'no'/'YES'
If "YES", alarm outputs will be listed.
drA - Adaptive tune enable
Makes it possible for the controller to employ the adaptive tune feature.
drA.t - Adaptive tune trigger level in display units. Range=1 to 9999
Once setpoint has been reached and control stabilized, adaptive tune trigger level is the distance away from setpoint at which the controller will initiate a self-tune. Adaptive tune is most beneficial in processes where conditions that affect change with some frequency.
FASt - Fast run through program (no/YES)
Permits user to quickly run through program and check if outputs turn off or on as programmed.
FOP - Forced manual output power
Provides choice or bumpless auto/manual; that is, when manual mode is selected, a predetermined output level will be activated.
FF.Pb - SP, or PV, feedforward proportional band
Feed forward is used for ratio control between two setpoints such as in a furnace temperature vs load temperature application (not to be confused with true cascade control).
FF.tr - Feedforward trim %
An offset that is added to or subtracted from the feedforward value.
Func (LA, LB, or LC)
Function of Digital Inputs used for logic functions. A switch (dry contact closure switch) can be installed which enables user to switch between the standard digital inputs functions. For example: select setpoint 2, activate self-tune, go to manual output, freeze integral calculations, etc.
Fwd.t - Feed forward type
Forward setpoint based on output power.
Gsch - Gain schedule enable
The PID values for one setpoint might not be appropriate for a setpoint which is significantly higher or lower than another. If enabled, this feature permits a second set of PID values to be used with a second setpoint which might be employed, for instance, at some point during a running program. (See SP.2 and PID.2) in Configuration section and SP2.L, SP2.H and SP 2 in operation section of manual.)
G.SP - PV at which transfer from 'PID.1' to 'PID.2' takes place
Used in conjunction with gain scheduling. When the characteristics of the process change and a new setpoint (setpoint 2) in entered for which former PID values are not appropriate, G.5P causes the second set of PID values to be used when setpoint is approached.
Hb - Holdback type (OFF, LO, HI or bAnd)
Present only in setpoint programming controllers. "Holds" the ramp/dwell program and waits for the furnace to "catch up". - Functions with Hb V (holdback value). Restricts holdback, if not turned OFF, to heating segments (Lo) or cooling segments (HI) of program, or can be set up to be employed during both heating and cooling segments (bAnd).
Hb.tY - Holdback Type for setpoint rate limit (OFF, Lo Hi, or bAnd)
Same as Hb, except that this holdback is activated, if needed, during a ramp to setpoint which takes place other than during the running of a program.
Hb V - Holdback value (display units)
Present only in setpoint programming controllers - Places a running program into a hold position. This occurs when the process variable deviates from setpoint by the amount established as the holdback value.
Hcb - High Cutback (setpoint 1)
During an auto-tune sequence, this parameter is automatically set by the controller. Hcb permits the user to set the value of this parameter that is activated during the tuning of a cooling control loop to prevent undershoot. If the control mode is auto, Hcb defaults to three times the proportional band.
Hcb2 - Used in gain scheduling.
See G.SP and Hcb.
HY1 (2, 3, and 4) - Alarm 1 (2, 3, and 4) Hysteresis (in display units)
Used to prevent alrm relay "chatter". The distance away from an alarm point that a process variable must travel before the alarm condition resets. For example: alarm=300 and HY=2. The alarm activates at 300 and will not clear until 298.
In 1 - In 8 - Input values for 8-point linearization
Enables user to customize input scaling across an 8-point curve. Intended for use with custom sensors.
Latching Alarm
A latching alarm remains in alarm condition until it is reset. A non-latching alarm resets itself as soon as the alarm ceases to exist. The alarm condition continues throughout the hysteresis value.
Lbt - Loop Break Time in seconds
When an output ceases to function correctly, loop break time determines the period of time which elapses before an alarm output changes state. For example: set Lbt at 300 seconds (5 minutes). If the temperature is below setpoint and the Eurotherm increases the output but nothing happens for 300 seconds, then the Lbt alarm will activate. Typical Lbt conditions: heat contactor is broken, fuse is blown or thermocouple was not put back into the machine.
Lcb - Cutback Low (setpoint 1)
During an auto tune sequence, this parameter is automatically set by the controller. Lcb permits the user to set value of this parameter which is activated during the tuning of a heating control loop to prevent overshoot. If the control mode is auto, Lcb defaults to three times the proportional band.
Lcb2 - Used in gain scheduling.
See G.SP and Lcb.
mV.1 - IP1 measured value (at terminals)
Displays the analog value of input 1. Eliminates the necessity of using a meter to verify the input. Also provides a means of determining if the sensing devise is wired backwards (will display negative value).
mV.2 - IP2 analog value (at terminals)
Only if DC input in Module 3 position. - Displays the analog value of input 2. See mV.1 above.
nSP - Number of setpoints - 2, or (in 2400s only) 4
This parameter permits selecting number of setpoints stored in memory in the non-programmer instruments. The programmer instruments automatically have 16 segments of ramp/dwell/ramp/… setpoint profiling.
ont.C - Cool output minimum on-line (secs). Auto (0.05s), or 1-999.9s
The minimum time cooling output is on when the controller is set to auto control mode. Some compressor or valves require a minimum on-time.
ont.H - Heat output minimum on-time (secs). Auto )0.05s), or 1-999.9s
The minimum time heating output is on when the controller is set auto control mode. Some Eurotherm solid state relays require a minimum on-time (such as .2 seconds) in order to read amperage or other partial load failure diagnostics.
OP.Lo - Low power limit (%)
Set to (-100) for cooling; to 0 for heating for most applications. Permits user to limit power if necessary.
OP.Hi - High power limit (%)
Set to 0 for cooling; to 100 for heating for most applications. Permits user to limit output power if necessary.
out.n - Event output states (OFF/on)
Establishes whether output is low or high during a program event.
Pb - Proportional Band in display units (setpoint 1)
The range of process values over which linear gain action occurs before the output saturates at maximum or minimum. Value should be as low as possible without causing oscillation.
Pb2 - Used in gain scheduling.
See G.SP and Pb.
Pd.tr - Burnpless Manual/Auto transfer when using PD control
When instrument control mode is switched from auto to manual, output may change dramatically, shocking the system (non-bumpless transfer). Selecting Pd.tr will cause output to change gradually so that the system is not shocked.
PwrF - Power Feedback
Enables controller to monitor and correct for fluctuations across the supply voltage. For example: in a "brownout", the instrument instantly increasing the output so the heaters continue to deliver the same BTUs even though the voltage has dropped. (Do not confuse this mnenomic with Pwr.F, power fail, in the programmer configuration.)
Pwr.F - Power fail recovery in the programmer list
Determines from what the instrument is to do if power is interrupted during the running of a program. (Three options: continue from last setpoint (SP; ramp, at last ramp rate, from PV to SP; or reset the program.)
rEL.C - Relative Cool Gain (setpoint 1)
Compensates for the different quantities of energy needed to heat, as opposed to that needed to cool, a process. For example: water cooling applications might be a rEL.C of 4 (cooling is 4 times faster than the heat-up process).
rEL.2 - Used in gain scheduling.
See G.SP and rEL.C.
rES - Manual Reset (%) (setpoint 1)
Provides an opportunity for the user perform the integral action rather than letting the controller automatically calculate the value.
rrES - Run/Reset
Digital input is open for run, closed for reset.
rESr - Reset/Run
Digital input is open for reset, closed for run.
rES.2 - Used in gain scheduling.
See G.SP and rES.
rm.SP - Remote setpoint
Analog signal brought in from another device.
rmt.t - Remote setpoint trim
An offset - added to or subtracted from analog signal brought in from another device.
Sb.OP - Sensor Break Output Power (%)
Default output power in the event a sensor-break condition arises.
Sbr.t - Sensor break output
Enables user to establish whether the output will freeze at the last output in existence at the time of a sensor break (open sensing device or other problem at input of instrument), or go to a pre-determined value.
SSEL - Select SP1 to SP16, depending on configuration
Permits the user to determine which setpoint will be displayed.
SSr1
If the Series 2000 has a LOGIC output board installed and if the heat contactor is a TE10S/PDS1 smart contactor, then selecting SSr1 permits the LOGIC board to activate the contactor AND monitor for alarms from the contactor.
SSr2
If the Series 2000 has a LOGIC output board installed and if the heat contactor is a TE10S/PDS2 smart contactor, then selecting SSr2 permits the LOGIC board to activate the contactor AND monitor for alarms from the contactor AND monitor the amperage flowing through the TE10S contactor.
Sync - Segment synchronization (no/YES)
If YES, causes program of two or more instruments to run synchronously. For example: instrument 1 is a temperature programmer and instrument 2 is a carbon potential programmer.
SYNC - Synchronizes program of two or more programmer instruments
If enabled, programs of two or more instruments can be linked (through setting Sync to YES in parameter list) through PDSIO to one clock so that the programs run simultaneously.
td - Derivative time in secs (setpoint 1)
Gives a fast response to large change in the process value which aids in improving process stability.
tdz - Used in gain scheduling.
See G.SP and td.
ti - integral time in secs (setpoint 1)
Helps to achieve zero steady-state control error by resetting the setpoint at intervals determined by integral time.
ti2 - Used in gain scheduling.
See G.SP and tl.
Val.L - Display reading low
Displays reading which corresponds to minimum linear input value - the low range of the sensing device.
Val.H - Display reading high
Displays which corresponds to maximum linear input value - the high range of the sensing device.
VAL.1 - VAL.3 - Display values corresponding to the 8 input values ( in 1 - in 8)
These 8 input characterize a custom, 8 point curve.
w.SP - Working setpoint
the setpoint during calculations. For example: the setpoint in a ramping controller may be 400 but the w.SP will be the calculated number which will be 200, 201, 202, etc.
w.OP - Working output
output level which is calculated by the control algorithm based upon the currently selected setpoint.

Last updated July 3, 2003