T630 Process Data Controller


TECHNICAL SPECIFICATION T630
General
Types available: V, mA (via external burden), thermocouple, 2/3-wire RTD
Characterisation: Linear, square root, thermocouple, RTD
Common mode rejection: 140dB
Series mode rejection: 60dB
Input isolation: 240V 50/60Hz working
PV sample rate: 8Hz
Resolution: 14 bits minimum
mA inputs
Ranges: 0-20mA, 4-20mA using external 50W burden resistor
Break protection: 0-20mA down; 4-20mA selectable up/down
Resolution: 14 bits min. (1.2µA)
Accuracy @25°C: 0.1% of range (excluding external burden resistor)
Temp drift/°C range: < ±[450µV + 0.007% of reading] @ 99% confidence;
< ±[50µV + 0.004% of reading]/°C typical

Thermocouple inputs
Thermocouples types: J, K, T, S, R, B, N
CJC accuracy: ±0.25°C (@ 25°C ± 5°C)
CJC ambient rejection: 30:1 typical

Voltage inputs
Ranges: 0-10V, 1-5V
Break protection: 0-10V pull-down; 1-5V selectable up/down
Input impedance: >245kW
Resolution: 14 bits min. (520µV)
Accuracy @25°C: 0.1% of range
Temperature drift/°C: < ±[500µV + 0.014% of reading] @ 99% confidence;
< ±[20µV + 0.006% of reading] typical

Resistance thermometer inputs (PRT)
Input type: 2- or 3-wire
Sensor type supported: Pt100
Range: –210 to +1200°C
Lead rejection (3-wire): 8mW/W of lead resistance
Sensor current: 250µA
Input impedance: >10MW
Resolution: 14 bits min. (0.16°C)
Accuracy @25°C: 0.1% of range
Temperature drift: < ±[2.4mW + 0.003% of reading] max;
< ±[0.6mW + 0.002% of reading] typical

Process (analogue) outputs
General isolation: 60V
Current outputs-----
Range: 0-20mA, 4-20mA
Over-/under- range: up to 22mA
Maximum load: 1kW
Resolution: 12 bits min. (5µA)
Accuracy @25°C: 0.5%
Temperature drift/°C: < ±[5µA + 0.03% of reading]
Voltage outputs (Consult factory)-----
Range: 0-10V, 1-5V
Over-/under- range: –1V to +11V
Maximum load: 10mA
Resolution: 12 bits min. (2.5mV)
Accuracy @25°C: 0.5%
Temperature drift/°C: < ±[0.5mV + 0.03% of reading]

Inputs and Outputs
I/O technology: Delta sigma.
Boards providing I/O: Main pcb, and (optional) I/O expansion pcb

Transmitter Power Supply
Voltage: 24V ±1.2V (up to 22mA)
Current: 0-22mA (limit at 30mA)
Isolation: 60V working

Analogue Inputs
Range: 0-10V, 1-5V
Over-/under- range: –1 to +11V
Break detection Selectable up/down scale or last value, response time
<1 sample period
Input impedance: >250kW
Resolution: 12 bits min. (3mV)
Accuracy @25°C: 0.1% of range
Temperature drift/°C: < ±[0.5mV + 0.014% of reading];
< ±[0.1mV + 0.008% of reading] typical

Analogue Outputs
Range: 0-10V, 1-5V
Over-/under- range: –1 to +11V
Maximum load: 10mA
Resolution: 12 bits min. (2.5µV)
Accuracy @25°C: 0.1% of range
Temperature drift/°C: < ±[0.5mV + 0.014% of reading];
< ±[0.1mV + 0.008% of reading] typical

Digital inputs
Pullup voltage: 24V dc via 12kW, or open-circuit (selectable)
Input thresholds: Logic 1: 6.5V minimum
Logic 0: 2.5V maximum

Digital outputs
Pullup voltage: 24V dc via 12k., or open-circuit (selectable)
Max. low-state current: 100mA
Max. external pullup voltage: 50V
Isolation: 60V dc working

Relays
Watchdog and alarm relays: SPST, open when de-energised (alarm condition)
Contact rating: 1A at 24V ac/dc. Absolute max. rating 2A at 60V
Isolation: 60V working

Control characteristics
General
Loop update time: 125ms total
Action on sensor failure: User-selectable – no mode change, or forced manual mode with selectable ‘failsafe’ output (last or low OP)
Power-fail recovery: User-selectable – last operating condition, or manual with selectable ‘failsafe’ output (last or low OP)

Control Algorithms
Type (user-selectable): Single Loop, Ratio, Dual Loop Cascade, Override, Manual Station
Control algorithm: Selectable for P, PI, PD, PID or ON/OFF; direct or inverse-acting
Control output: 0-100% for direct or reverse acting actuator; raise/lower output for incremental actuators
Autotune: Single-shot self tune, PID terms freeze after defined period

Serial communications
MODBUS
Standard: RS422 (5-wire) or RS485 (3-wire)
Data rate: Selectable 1200-19,200 bits/sec
Data format: 8 bit, selectable parity, 1/2 stop bits Storage temperature: –10°C to +85°C
Protocol: MODBUS/J-BUS RTU (slave)
Line impedance: 120W-240W twisted pair
Line length: 1220m maximum at 9600 baud
Units per line: 16 instruments max electrical loading, expandable to 128 by use of buffers

Fieldbus communications
PROFIBUS-DP
Physical Medium: 2-wire RS485
Network Topology: Linear bus with active termination of bus at both ends
Protocol: PROFIBUS –DP, intelligent slave
Number of stations: 32 per network segment up to 127 with repeaters

Configuration
Parameters storage: Non-volatile EEPROM
Front panel: Parameter access by list: loop 1, loop 2, general, comms, main I/O, expansion I/O and calibration
Access protection: Operator parameters with no password. Control and instrument parameters via separate passwords
PC (via configuration adaptor): Plugs into side of unpowered unit via RJ11 connector

Fascia
Display technology: LED
Bargraph Displays: 2 vertical, 51 segment LED for PV-X (red) and SP-W (green); Display in 2% steps 1 horizontal, 10 segment LED for OP-Y (yellow); Display in 10% steps
Numeric Displays: 4 1/2 digit display (red) with decimal point.
Alphanumeric display: 2 character 14 segment starburst LEDs for parameter identification or error 19999 resolution
Alarm/status displays: LEDs (green/yellow/red)
Push-buttons: Elastomeric with orange legend
Loop Tag/Service identification: Write-on label (white) at top of fascia

Physical
Dimensions: 72mm × 144mm × 252.55mm (including keypads)
Weight: 1.39kg
MTBF 20 years
Terminals type: Clamping screw with cable protector
Maximum wire/ferrule size: 2.5mm2

Power Supplies
Mains version
Voltage range: 90-265V ac rms
Frequency range: 45-65Hz
Power rating: 25VA
Hold up time: 20ms
Fuse: Factory replacement only
DC version
I/P voltage range: 19-55V dc
Power rating: 25VA
Hold up time: 20ms
Fuse: Factory replacement only